Timedora

Thermal Resistance Networks

A practical guide to modeling steady one-dimensional heat transfer with thermal-resistance networks, including composite plane walls and cylindrical insulation.

Build and solve the network

Model heat flow as a resistance network

A thermal-resistance network is an accounting tool for steady, predominantly one-dimensional heat transfer. Temperature difference is the driving potential, heat-transfer rate Q˙\dot Q is the flow, and thermal resistance opposes that flow. For a series path,

Rtotal=∑iRi,Q˙=Thot−TcoldRtotal.R_{\mathrm{total}}=\sum_i R_i, \qquad \dot Q=\frac{T_{\mathrm{hot}}-T_{\mathrm{cold}}}{R_{\mathrm{total}}}.

The standard resistance formulas assume constant material properties. The model also assumes there is no energy generation within the layers. Use consistent SI units: resistance is in K/W and heat rate is in W.

Build the path and solve it

First identify the heat-flow path and mark the bulk-fluid temperatures, surfaces, and material interfaces. Add a resistance for each convection film and each conduction layer. For convection over area AA,

Rconv=1hA,R_{\mathrm{conv}}=\frac{1}{hA},

where hh is the convection coefficient. Then add resistances along a series path and divide the end-to-end temperature difference by their total.

Every series element carries the same heat rate. Its temperature drop is ΔTi=Q˙Ri\Delta T_i=\dot Q R_i. Starting at the hot end, subtract each drop in turn to find the successive surface and interface temperatures. Distinct parallel heat-flow paths are different: combine their resistances by 1/Req=∑j1/Rj1/R_{\mathrm{eq}}=\sum_j 1/R_j, then treat the equivalent resistance as part of the overall network.

Check the result

Confirm that series elements carry the same Q˙\dot Q, and that separate branches were treated as parallel paths. In passive series layers, temperatures should change monotonically from hot to cold. The largest resistance should have the largest temperature drop. Include contact resistance as another series element only when specified or physically justified; it can produce a temperature jump at an interface.

Composite plane walls

Add the films and layers

For a plane layer, conduction resistance is

Rplane=LkA,R_{\mathrm{plane}}=\frac{L}{kA},

where LL is thickness, kk is thermal conductivity, and AA is area. For a composite wall between two fluids, add the hot-side convection resistance, each layer’s conduction resistance, and the cold-side convection resistance:

Rtotal=1h1A+∑jLjkjA+1h2A,Q˙=T∞,1−T∞,2Rtotal.R_{\mathrm{total}}=\frac{1}{h_1A}+\sum_j\frac{L_j}{k_jA}+\frac{1}{h_2A}, \qquad \dot Q=\frac{T_{\infty,1}-T_{\infty,2}}{R_{\mathrm{total}}}.

Each layer has its own thickness and conductivity. The layers share the same area when the wall is plane and edge effects are insignificant.

Worked example: a two-layer wall

The source example has a 10 m² wall between fluids at 200°C and 20°C. From hot to cold, it has a 0.10 m layer with k=0.8 W/(m K)k=0.8\,\mathrm{W/(m\,K)}, then 0.05 m of insulation with k=0.04 W/(m K)k=0.04\,\mathrm{W/(m\,K)}. The convection coefficients are h1=10h_1=10 and h2=25 W/(m2 K)h_2=25\,\mathrm{W/(m^2\,K)}.

Substitute the data into each resistance formula:

Rh1=110(10)=0.0100 K/W,R1=0.100.8(10)=0.0125 K/W,Rins=0.050.04(10)=0.1250 K/W,Rh2=125(10)=0.0040 K/W.\begin{aligned} R_{h_1}&=\frac{1}{10(10)}=0.0100\ \mathrm{K/W},\\ R_1&=\frac{0.10}{0.8(10)}=0.0125\ \mathrm{K/W},\\ R_{\mathrm{ins}}&=\frac{0.05}{0.04(10)}=0.1250\ \mathrm{K/W},\\ R_{h_2}&=\frac{1}{25(10)}=0.0040\ \mathrm{K/W}. \end{aligned}

Adding them gives Rtotal=0.1515 K/WR_{\mathrm{total}}=0.1515\,\mathrm{K/W}, so

Q˙=200−200.1515≈1.19×103 W.\dot Q=\frac{200-20}{0.1515}\approx1.19\times10^3\,\mathrm W.

To get each temperature, subtract Q˙Ri\dot Q R_i successively from 200°C. The temperatures after the hot film, first layer, insulation, and cold film are approximately 188.1°C, 173.3°C, 24.8°C, and 20°C. The insulation has the largest resistance, so it accounts for most of the temperature drop. The table shows the approximate drop across each element.

Temperature drops across the wall
ElementR (K/W)Drop (°C)After (°C)
Hot-side convection0.010011.9188.1
Solid layer0.012514.9173.3
Insulation0.1250148.524.8
Cold-side convection0.00404.820.0
Approximate resistance drops and temperatures for the 10 m² composite-wall example, proceeding from the hot fluid to the cold fluid.

Cylindrical walls and insulation

Use cylindrical resistance

In a cylinder, the area available for radial heat flow changes with radius. That is why conduction resistance is logarithmic rather than the plane-wall expression:

Rcyl=ln⁡(ro/ri)2πkℓ,R_{\mathrm{cyl}}=\frac{\ln(r_o/r_i)}{2\pi k\ell},

where rir_i and ror_o are the layer’s inner and outer radii, kk is conductivity, and ℓ\ell is length. Use the actual radius ratio; insulation thickness by itself is not enough to determine this resistance.

For concentric layers, calculate each layer’s resistance using its own inner and outer radii. Add these conduction resistances in series with the convection films. The inside convection area is 2πriℓ2\pi r_i\ell, while the outside convection area is 2πroℓ2\pi r_o\ell; use the radius of the corresponding surface. Once the total resistance is known, divide the fluid temperature difference by it to find Q˙\dot Q. Then subtract Q˙Ri\dot Q R_i at each step to obtain interface temperatures.

Worked example: an insulated pipe

The source example specifies a 5 m pipe with inner radius 0.05 m, outer radius 0.06 m, and conductivity 15 W/(m K)15\,\mathrm{W/(m\,K)}. Insulation extends to radius 0.10 m and has conductivity 0.05 W/(m K)0.05\,\mathrm{W/(m\,K)}. The fluid and surroundings are at 150°C and 25°C; hi=200h_i=200 and ho=10 W/(m2 K)h_o=10\,\mathrm{W/(m^2\,K)}.

Using those stated coefficients and the corresponding cylindrical areas, the resistances are

Rhi=1200(2π)(0.05)(5)≈0.003183 K/W,Rpipe=ln⁡(0.06/0.05)2π(15)(5)≈0.000387 K/W,Rins=ln⁡(0.10/0.06)2π(0.05)(5)≈0.3252 K/W,Rho=110(2π)(0.10)(5)≈0.03183 K/W.\begin{aligned} R_{h_i}&=\frac{1}{200(2\pi)(0.05)(5)}\approx0.003183\ \mathrm{K/W},\\ R_{\mathrm{pipe}}&=\frac{\ln(0.06/0.05)}{2\pi(15)(5)}\approx0.000387\ \mathrm{K/W},\\ R_{\mathrm{ins}}&=\frac{\ln(0.10/0.06)}{2\pi(0.05)(5)}\approx0.3252\ \mathrm{K/W},\\ R_{h_o}&=\frac{1}{10(2\pi)(0.10)(5)}\approx0.03183\ \mathrm{K/W}. \end{aligned}

The total is about 0.3606 K/W0.3606\,\mathrm{K/W}, giving Q˙≈(150−25)/0.3606≈346.6 W\dot Q\approx(150-25)/0.3606\approx346.6\,\mathrm W. Subtracting each successive Q˙Ri\dot Q R_i drop gives a pipe outer surface near 148.8°C and an insulation outer surface near 36.1°C. The insulation resistance is much larger than the other resistances, so most of the temperature drop occurs there. The table traces the approximate drops from the hot fluid to the surroundings.

These results use the example’s stated geometry and convection coefficients. The source passage’s listed convection resistances and resulting heat rate are inconsistent with those inputs.

Temperature drops across the pipe
ElementR (K/W)Drop (°C)After (°C)
Inside convection0.0031831.10148.9
Pipe conduction0.0003870.13148.8
Insulation conduction0.3252112.736.1
Outside convection0.0318311.0325.0
Approximate values recalculated from the stated 5 m pipe geometry and convection coefficients, proceeding from the 150°C fluid toward the 25°C surroundings. The recalculated convection resistances differ from those reported in the source passage.