What environmental risks do CFCs, HCFCs, and many HFCs pose?

Back

CFCs and HCFCs can deplete the ozone layer; many HFCs do not, but can have high global-warming potential.

02
Front

What does Clean Air Act Section 608 regulate?

Back

Section 608 regulates stationary refrigeration and air-conditioning work through certification, venting prohibitions, and recovery, leak-repair, sales, and recordkeeping requirements.

03
Front

What are the AIM Act’s main approaches to HFCs?

Back

The AIM Act phases down HFCs, restricts their use in specific sectors, and sets rules to reduce emissions and increase reclamation.

04
Front

When does refrigerant work generally require Section 608 certification?

Back

Certification is generally required for work reasonably expected to release refrigerant, such as attaching or detaching gauges or hoses, or adding or removing refrigerant.

05
Front

What equipment does Universal Section 608 certification cover?

Back

Type I, II, and III certifications cover specified equipment; Universal certification covers all types.

06
Front

What is the de minimis venting exception during refrigerant recovery?

Back

Technicians must recover refrigerant rather than intentionally vent it. A narrow de minimis exception covers small releases during good-faith recovery, such as normal hose connection or disconnection.

07
Front

When may recovered refrigerant be sold for reuse?

Back

Recovered refrigerant generally cannot be sold for reuse unless reclaimed by an EPA-certified reclaimer. Reuse may be allowed in equipment belonging to the same owner, subject to applicable requirements.

08
Front

Which appliances are covered by Section 608 leak-repair provisions?

Back

Section 608 leak-repair provisions apply to appliances with a full charge of at least 50 pounds of CFC or HCFC refrigerant; they do not apply under Section 608 to equipment containing only HFC substitutes.

09
Front

What is the AIM Act leak-rule threshold and a key exception?

Back

Effective January 1, 2026, the AIM Act rule covers certain appliances with at least 15 pounds of HFC or specified HFC-substitute refrigerant. Exceptions include residential and light-commercial air-conditioning and heat-pump equipment.

10
Front

What leak-rate thresholds apply by equipment category?

Back

The applicable thresholds are 30%30\% for industrial process refrigeration, 20%20\% for commercial refrigeration, and 10%10\% for comfort cooling and other covered categories.

11
Front

How soon must excess leaks generally be repaired?

Back

If the leak rate exceeds the applicable threshold, leaks generally must be identified and repaired within 30 days, or within 120 days if an industrial-process shutdown is required. Verification tests are also required.

12
Front

What disposal records must technicians keep for appliances with 5 to 50 pounds of refrigerant?

Back

For disposal of appliances containing 5 to 50 pounds of refrigerant, technicians record the recovery location and date, refrigerant type, monthly amounts recovered, and amounts transferred for reclamation or destruction; keep these records for three years.