Timedora
Free Online Flashcard Deck

Heat Exchanger Analysis Flashcards Free Online Flashcards

Study Heat Exchanger Analysis with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

When is the LMTD method useful?

Back

Use LMTD when inlet and outlet temperatures are known, often to determine required area or check performance.

02
Front

What effectiveness relation applies to single-pass parallel flow?

Back

For a single-pass parallel-flow exchanger, use ε=1−exp⁡[−NTU(1+Cr)]1+Cr\varepsilon=\frac{1-\exp[-\mathrm{NTU}(1+C_r)]}{1+C_r}.

03
Front

How does effectiveness determine heat-transfer rate?

Back

Effectiveness is the fraction of maximum possible heat transfer achieved: ε=Q˙Q˙max⁡\varepsilon=\frac{\dot Q}{\dot Q_{\max}}, so Q˙=εCmin⁡(Th,i−Tc,i)\dot Q=\varepsilon C_{\min}(T_{h,i}-T_{c,i}).

04
Front

How are flat-wall thermal resistances combined to find UU?

Back

For a thin, flat wall with negligible fouling, 1U≈1hh+tkw+1hc\frac{1}{U}\approx\frac{1}{h_h}+\frac{t}{k_w}+\frac{1}{h_c}. Add fouling resistances when relevant.

05
Front

When is effectiveness–NTU useful?

Back

Use effectiveness–NTU when inlet temperatures and UAUA are known but outlet temperatures are unknown; find NTU and effectiveness, then calculate heat transfer and outlet temperatures.

06
Front

How do you calculate stream outlet temperatures from Q˙\dot Q?

Back

With negligible external heat loss and no phase change, Th,o=Th,i−Q˙ChT_{h,o}=T_{h,i}-\frac{\dot Q}{C_h} and Tc,o=Tc,i+Q˙CcT_{c,o}=T_{c,i}+\frac{\dot Q}{C_c}.

07
Front

At equal NTU and CrC_r, which arrangement is generally more effective?

Back

At the same NTU and capacity-rate ratio, counterflow is generally more effective than parallel flow.

08
Front

What does UAUA represent when a consistent reference area is used?

Back

With a consistent reference area, UAUA is the exchanger’s overall thermal conductance.

09
Front

How should fouling affect the overall resistance calculation?

Back

Include fouling resistances in the overall resistance calculation when fouling is relevant.

10
Front

What is the LMTD heat-transfer relation for a simple exchanger?

Back

For a simple exchanger, Q˙=UAFΔTlm\dot Q=UA F\Delta T_{\mathrm{lm}}, where ΔTlm=ΔT1−ΔT2ln⁡(ΔT1/ΔT2)\Delta T_{\mathrm{lm}}=\frac{\Delta T_1-\Delta T_2}{\ln(\Delta T_1/\Delta T_2)}.

11
Front

How is capacity-rate ratio CrC_r defined?

Back

The capacity-rate ratio is Cr=Cmin⁡Cmax⁡C_r=\frac{C_{\min}}{C_{\max}}, with Cmin⁡C_{\min} and Cmax⁡C_{\max} the smaller and larger stream capacity rates.

12
Front

What determines the maximum possible heat-transfer rate?

Back

The maximum possible transfer is Q˙max⁡=Cmin⁡(Th,i−Tc,i)\dot Q_{\max}=C_{\min}(T_{h,i}-T_{c,i}); the smaller capacity rate limits the streams’ temperature changes.