Heat Exchanger Effectiveness–NTU Analysis

A practical guide to estimating exchanger conductance, predicting heat transfer and outlet temperatures, and choosing the appropriate analysis method.

From heat-transfer resistances to conductance

From fluid-side convection to an overall coefficient

Heat travels from the hot fluid to the cold fluid through several resistances: convection at the hot-fluid side, conduction through the separating wall, and convection at the cold-fluid side. To estimate the two convection coefficients, use heat-transfer correlations suited to the exchanger geometry and flow. Such correlations commonly relate the Nusselt number to Reynolds and Prandtl numbers, with fluid properties evaluated at a representative temperature.

For a thin, flat wall with negligible fouling, the resistances combine as

1U≈1hh+tkw+1hc,\frac{1}{U} \approx \frac{1}{h_h} + \frac{t}{k_w} + \frac{1}{h_c},

where hhh_h and hch_c are the hot- and cold-side convection coefficients, tt is wall thickness, and kwk_w is wall conductivity. Fouling adds resistance and should be included when relevant. Because these are resistances in series, a substantial resistance on either fluid side or in the wall can limit the overall heat transfer.

The coefficient UU is expressed per unit area. Use a consistent reference area when combining resistances and forming UAUA; their product is the exchanger’s . The displayed relation is a simplified flat-wall expression: cylindrical walls or unequal inside and outside reference areas require the corresponding area-based resistance relation instead.

Use NTU and to predict performance

Set up the capacity rates and NTU

The –NTU method is useful when inlet temperatures and exchanger conductance UAUA are known but outlet temperatures are not. First calculate the of each stream:

Ch=m˙hcp,h,Cc=m˙ccp,c.C_h=\dot m_h c_{p,h}, \qquad C_c=\dot m_c c_{p,c}.

For single-phase streams with approximately constant specific heats, identify

Cmin⁡=min⁡(Ch,Cc),Cmax⁡=max⁡(Ch,Cc),Cr=Cmin⁡Cmax⁡.C_{\min}=\min(C_h,C_c), \qquad C_{\max}=\max(C_h,C_c), \qquad C_r=\frac{C_{\min}}{C_{\max}}.

The smaller capacity rate limits how much either stream can change temperature for a given heat transfer. Next compare the exchanger conductance with that limiting rate:

NTU=UACmin⁡.\mathrm{NTU}=\frac{UA}{C_{\min}}.

A larger NTU generally corresponds to greater , but NTU alone does not determine it: the capacity-rate ratio and flow arrangement also matter.

Choose the relation for the flow arrangement

For single-pass parallel flow, the two streams travel in the same direction, and

εparallel=1−exp⁡[−NTU(1+Cr)]1+Cr.\varepsilon_{\mathrm{parallel}}= \frac{1-\exp[-\mathrm{NTU}(1+C_r)]}{1+C_r}.

For counterflow, the streams travel in opposite directions. When Cr≠1C_r\ne 1, use

εcounter=1−exp⁡[−NTU(1−Cr)]1−Crexp⁡[−NTU(1−Cr)].\varepsilon_{\mathrm{counter}}= \frac{1-\exp[-\mathrm{NTU}(1-C_r)]} {1-C_r\exp[-\mathrm{NTU}(1-C_r)]}.

The equal-capacity-rate case needs its own counterflow expression; substituting Cr=1C_r=1 into the preceding form gives an indeterminate expression. Use instead

εcounter=NTU1+NTU(Cr=1).\varepsilon_{\mathrm{counter}}=\frac{\mathrm{NTU}}{1+\mathrm{NTU}} \qquad (C_r=1).

At the same NTU and capacity-rate ratio, counterflow is generally more effective than parallel flow. Crossflow and multipass shell-and-tube exchangers may have different flow and mixing arrangements, so use a relation or chart appropriate to that configuration rather than assuming one of these simple single-pass formulas.

Convert into heat transfer and outlet temperatures

The greatest possible heat-transfer rate, for the stated single-phase, approximately constant-specific-heat model, is

Q˙max⁡=Cmin⁡(Th,i−Tc,i).\dot Q_{\max}=C_{\min}(T_{h,i}-T_{c,i}).

is the fraction of this maximum achieved, so

ε=Q˙Q˙max⁡,Q˙=εCmin⁡(Th,i−Tc,i).\varepsilon=\frac{\dot Q}{\dot Q_{\max}}, \qquad \dot Q=\varepsilon C_{\min}(T_{h,i}-T_{c,i}).

For an ordinary passive exchanger, lies between zero and one. Once Q˙\dot Q is known, apply an energy balance to each stream:

Th,o=Th,i−Q˙Ch,Tc,o=Tc,i+Q˙Cc.T_{h,o}=T_{h,i}-\frac{\dot Q}{C_h}, \qquad T_{c,o}=T_{c,i}+\frac{\dot Q}{C_c}.

These outlet relations assume negligible heat loss to the surroundings and no phase change. They express the same transferred heat from opposite sides: the hot stream loses Q˙\dot Q, while the cold stream gains Q˙\dot Q. Phase-changing streams need an appropriate energy balance and heat-capacity treatment; the formulas above should not be applied without that adjustment.

Worked example: counterflow exchanger

A counterflow exchanger has UA=2 kW/KUA=2\ \mathrm{kW/K}, Ch=2 kW/KC_h=2\ \mathrm{kW/K}, and Cc=1 kW/KC_c=1\ \mathrm{kW/K}. The inlet temperatures are Th,i=150∘CT_{h,i}=150^\circ\mathrm C and Tc,i=20∘CT_{c,i}=20^\circ\mathrm C. Find the heat-transfer rate and outlet temperatures.

First, the smaller capacity rate is Cmin⁡=1 kW/KC_{\min}=1\ \mathrm{kW/K}, and the ratio is Cr=1/2=0.5C_r=1/2=0.5. Thus

NTU=2 kW/K1 kW/K=2.\mathrm{NTU}=\frac{2\ \mathrm{kW/K}}{1\ \mathrm{kW/K}}=2.

Since this is counterflow and Cr≠1C_r\ne1, use the counterflow relation:

ε=1−e−2(1−0.5)1−0.5e−2(1−0.5)=1−e−11−0.5e−1≈0.775.\varepsilon= \frac{1-e^{-2(1-0.5)}}{1-0.5e^{-2(1-0.5)}} =\frac{1-e^{-1}}{1-0.5e^{-1}} \approx0.775.

The inlet temperature difference is 150−20=130 K150-20=130\ \mathrm K. Therefore,

Q˙=0.775(1 kW/K)(130 K)≈100.7 kW.\dot Q=0.775(1\ \mathrm{kW/K})(130\ \mathrm K)\approx100.7\ \mathrm{kW}.

Now use each stream’s capacity rate to find its temperature change:

Tc,o=20∘C+100.7 kW1 kW/K≈120.7∘C,T_{c,o}=20^\circ\mathrm C+\frac{100.7\ \mathrm{kW}}{1\ \mathrm{kW/K}}\approx120.7^\circ\mathrm C,
Th,o=150∘C−100.7 kW2 kW/K≈99.7∘C.T_{h,o}=150^\circ\mathrm C-\frac{100.7\ \mathrm{kW}}{2\ \mathrm{kW/K}}\approx99.7^\circ\mathrm C.

The cold outlet is warmer than the hot outlet, but it remains below the hot inlet temperature. That is possible in counterflow because the streams move in opposite directions. The energy balance also checks: the hot stream’s temperature drop corresponds to (2 kW/K)(150−99.7 K)≈100.6 kW(2\ \mathrm{kW/K})(150-99.7\ \mathrm K)\approx100.6\ \mathrm{kW}, while the cold stream’s rise corresponds to (1 kW/K)(120.7−20 K)≈100.7 kW(1\ \mathrm{kW/K})(120.7-20\ \mathrm K)\approx100.7\ \mathrm{kW}. The small difference is due to rounding; both represent the same heat transfer.

Choose between LMTD and –NTU

Match the method to the information available

Use the LMTD method when inlet and outlet temperatures are known. It is often used to determine required exchanger area or check performance. For a simple exchanger, with a correction factor FF when needed,

Q˙=UAFΔTlm,ΔTlm=ΔT1−ΔT2ln⁡(ΔT1/ΔT2),\dot Q=UA F\Delta T_{\mathrm{lm}}, \qquad \Delta T_{\mathrm{lm}}= \frac{\Delta T_1-\Delta T_2}{\ln(\Delta T_1/\Delta T_2)},

where ΔT1\Delta T_1 and ΔT2\Delta T_2 are the terminal temperature differences.

Use –NTU when inlet temperatures and UAUA are known but outlet temperatures are not. Calculate capacity rates and NTU, select the relation for the flow arrangement, and then determine heat transfer and outlet temperatures using energy balances.

When all terminal temperatures are known and the assumptions match, the two methods should give the same heat-transfer rate: they are different ways of analyzing the same exchanger performance. For crossflow or multipass equipment, use the appropriate configuration relation or LMTD correction factor. A simple parallel- or counterflow relation may not represent the actual flow and mixing arrangement.

  • : The relating heat transfer to area and temperature difference.

  • : A measure used with capacity-rate ratio and flow arrangement to determine exchanger .

  • : A representative mean temperature difference calculated from the exchanger’s terminal temperature differences.