Heat Exchanger Effectiveness–NTU Analysis
A practical guide to estimating exchanger conductance, predicting heat transfer and outlet temperatures, and choosing the appropriate analysis method.
From heat-transfer resistances to conductance
From fluid-side convection to an overall coefficient
Heat travels from the hot fluid to the cold fluid through several resistances: convection at the hot-fluid side, conduction through the separating wall, and convection at the cold-fluid side. To estimate the two convection coefficients, use heat-transfer correlations suited to the exchanger geometry and flow. Such correlations commonly relate the Nusselt number to Reynolds and Prandtl numbers, with fluid properties evaluated at a representative temperature.
For a thin, flat wall with negligible fouling, the resistances combine as
where and are the hot- and cold-side convection coefficients, is wall thickness, and is wall conductivity. Fouling adds resistance and should be included when relevant. Because these are resistances in series, a substantial resistance on either fluid side or in the wall can limit the overall heat transfer.
The coefficient is expressed per unit area. Use a consistent reference area when combining resistances and forming ; their product is the exchanger’s . The displayed relation is a simplified flat-wall expression: cylindrical walls or unequal inside and outside reference areas require the corresponding area-based resistance relation instead.
Use NTU and to predict performance
Set up the capacity rates and NTU
The –NTU method is useful when inlet temperatures and exchanger conductance are known but outlet temperatures are not. First calculate the of each stream:
For single-phase streams with approximately constant specific heats, identify
The smaller capacity rate limits how much either stream can change temperature for a given heat transfer. Next compare the exchanger conductance with that limiting rate:
A larger NTU generally corresponds to greater , but NTU alone does not determine it: the capacity-rate ratio and flow arrangement also matter.
Choose the relation for the flow arrangement
For single-pass parallel flow, the two streams travel in the same direction, and
For counterflow, the streams travel in opposite directions. When , use
The equal-capacity-rate case needs its own counterflow expression; substituting into the preceding form gives an indeterminate expression. Use instead
At the same NTU and capacity-rate ratio, counterflow is generally more effective than parallel flow. Crossflow and multipass shell-and-tube exchangers may have different flow and mixing arrangements, so use a relation or chart appropriate to that configuration rather than assuming one of these simple single-pass formulas.
Convert into heat transfer and outlet temperatures
The greatest possible heat-transfer rate, for the stated single-phase, approximately constant-specific-heat model, is
is the fraction of this maximum achieved, so
For an ordinary passive exchanger, lies between zero and one. Once is known, apply an energy balance to each stream:
These outlet relations assume negligible heat loss to the surroundings and no phase change. They express the same transferred heat from opposite sides: the hot stream loses , while the cold stream gains . Phase-changing streams need an appropriate energy balance and heat-capacity treatment; the formulas above should not be applied without that adjustment.
Worked example: counterflow exchanger
A counterflow exchanger has , , and . The inlet temperatures are and . Find the heat-transfer rate and outlet temperatures.
First, the smaller capacity rate is , and the ratio is . Thus
Since this is counterflow and , use the counterflow relation:
The inlet temperature difference is . Therefore,
Now use each stream’s capacity rate to find its temperature change:
The cold outlet is warmer than the hot outlet, but it remains below the hot inlet temperature. That is possible in counterflow because the streams move in opposite directions. The energy balance also checks: the hot stream’s temperature drop corresponds to , while the cold stream’s rise corresponds to . The small difference is due to rounding; both represent the same heat transfer.
Choose between LMTD and –NTU
Match the method to the information available
Use the LMTD method when inlet and outlet temperatures are known. It is often used to determine required exchanger area or check performance. For a simple exchanger, with a correction factor when needed,
where and are the terminal temperature differences.
Use –NTU when inlet temperatures and are known but outlet temperatures are not. Calculate capacity rates and NTU, select the relation for the flow arrangement, and then determine heat transfer and outlet temperatures using energy balances.
When all terminal temperatures are known and the assumptions match, the two methods should give the same heat-transfer rate: they are different ways of analyzing the same exchanger performance. For crossflow or multipass equipment, use the appropriate configuration relation or LMTD correction factor. A simple parallel- or counterflow relation may not represent the actual flow and mixing arrangement.
: The relating heat transfer to area and temperature difference.
: A measure used with capacity-rate ratio and flow arrangement to determine exchanger .
: A representative mean temperature difference calculated from the exchanger’s terminal temperature differences.