Heat Exchanger Energy Balances and LMTD
A practical guide to heat-exchanger energy balances, temperature driving forces, and configuration effects.
From Stream Temperatures to LMTD
Start with the energy balance
Heat passes through the separating wall from the hotter stream to the colder one. For steady operation with negligible heat loss to the surroundings, the heat-transfer rate calculated from either stream must agree:
Here, is mass flow rate, is specific heat capacity, and the inlet and outlet temperatures describe each stream’s change. The hot stream cools, while the cold stream warms. If properties vary substantially or a stream changes phase, use enthalpy differences rather than .
Match the terminal differences to the flow
The streams’ temperatures—and therefore their local difference —vary along the exchanger. In parallel flow, both streams enter at the same end and travel in the same direction. In counterflow, they enter at opposite ends. The terminal differences must be defined to match that arrangement:
For heat to flow from hot to cold throughout a simple exchanger, both terminal differences must be positive. A zero difference is a limiting case; a negative one signals a local reversal of the assumed heat-flow direction. For the same terminal temperatures, counterflow generally provides a larger mean temperature difference than parallel flow.
Calculate LMTD and heat-transfer rate
Because the local temperature difference is not generally constant, the standard heat-transfer equation uses its logarithmic mean:
where is the overall heat-transfer coefficient and is the corresponding area. If the terminal differences are equal, their common value is the LMTD. Temperature differences can be in kelvins or degrees Celsius, or in degrees Fahrenheit, as long as units are consistent.
Worked counterflow example. A hot stream goes from to , and a cold stream from to . First use the counterflow pairings:
Then . With and ,
The key is to choose the correct terminal differences before evaluating the logarithmic mean.
Interpreting a
Check the ends, not just the outlets
A means . This does not, by itself, mean heat has reversed direction: the outlet temperatures are at opposite ends in counterflow, so compare the hot and cold temperatures at each actual end. Heat can still flow from hot to cold throughout if both counterflow terminal differences are positive:
Illustrative hypothetical application: let the hot stream enter at 200 and leave at 110, while the cold stream enters at 70 and leaves at 130, all in the same temperature unit. Although , the counterflow terminal differences are and . Both are positive, so these outlet values do not imply a local reversal of the intended heat flow. A simple parallel-flow exchanger cannot sustain an outlet .
Correcting for Exchanger Configuration
Adjust the counterflow driving force
Multipass shell-and-tube and crossflow exchangers do not have a purely parallel- or counterflow temperature profile. For these configurations, first calculate the counterflow LMTD from the four stream temperatures, then apply the :
The factor depends on exchanger configuration and temperature ratios; obtain it from the appropriate chart or a validated calculation method for that configuration. For ideal parallel- or counterflow double-pipe exchangers, . For many multipass and crossflow designs, , so the corrected driving force is smaller than the counterflow value. A small factor indicates a substantially reduced effective driving force and may mean that more heat-transfer area or a different arrangement is needed.
: The temperature difference between the hot and cold streams at one end of the exchanger.
: A logarithmic average of the two terminal temperature differences, used as the mean temperature driving force in the standard heat-transfer equation.