Heat Exchanger Energy Balances and LMTD

A practical guide to heat-exchanger energy balances, temperature driving forces, and configuration effects.

From Stream Temperatures to LMTD

Start with the energy balance

Heat passes through the separating wall from the hotter stream to the colder one. For steady operation with negligible heat loss to the surroundings, the heat-transfer rate calculated from either stream must agree:

Q˙=m˙hcp,h(Th,i−Th,o)=m˙ccp,c(Tc,o−Tc,i).\dot Q=\dot m_h c_{p,h}(T_{h,i}-T_{h,o}) =\dot m_c c_{p,c}(T_{c,o}-T_{c,i}).

Here, m˙\dot m is mass flow rate, cpc_p is specific heat capacity, and the inlet and outlet temperatures describe each stream’s change. The hot stream cools, while the cold stream warms. If properties vary substantially or a stream changes phase, use enthalpy differences rather than cpΔTc_p\Delta T.

Match the terminal differences to the flow

The streams’ temperatures—and therefore their local difference Th−TcT_h-T_c—vary along the exchanger. In parallel flow, both streams enter at the same end and travel in the same direction. In counterflow, they enter at opposite ends. The terminal differences must be defined to match that arrangement:

Parallel flow: ΔT1=Th,i−Tc,i,ΔT2=Th,o−Tc,o,Counterflow: ΔT1=Th,i−Tc,o,ΔT2=Th,o−Tc,i.\begin{aligned} \text{Parallel flow: }&\Delta T_1=T_{h,i}-T_{c,i},\quad \Delta T_2=T_{h,o}-T_{c,o},\\ \text{Counterflow: }&\Delta T_1=T_{h,i}-T_{c,o},\quad \Delta T_2=T_{h,o}-T_{c,i}. \end{aligned}

For heat to flow from hot to cold throughout a simple exchanger, both terminal differences must be positive. A zero difference is a limiting case; a negative one signals a local reversal of the assumed heat-flow direction. For the same terminal temperatures, counterflow generally provides a larger mean temperature difference than parallel flow.

Calculate LMTD and heat-transfer rate

Because the local temperature difference is not generally constant, the standard heat-transfer equation uses its logarithmic mean:

ΔTlm=ΔT1−ΔT2ln⁡(ΔT1/ΔT2),Q˙=UAΔTlm,\Delta T_{lm}=\frac{\Delta T_1-\Delta T_2}{\ln(\Delta T_1/\Delta T_2)}, \qquad \dot Q=UA\Delta T_{lm},

where UU is the overall heat-transfer coefficient and AA is the corresponding area. If the terminal differences are equal, their common value is the LMTD. Temperature differences can be in kelvins or degrees Celsius, or in degrees Fahrenheit, as long as units are consistent.

Worked counterflow example. A hot stream goes from 200∘F200^\circ\mathrm F to 145∘F145^\circ\mathrm F, and a cold stream from 80∘F80^\circ\mathrm F to 120∘F120^\circ\mathrm F. First use the counterflow pairings:

ΔT1=200−120=80∘F,ΔT2=145−80=65∘F.\Delta T_1=200-120=80^\circ\mathrm F,\qquad \Delta T_2=145-80=65^\circ\mathrm F.

Then ΔTlm=(80−65)/ln⁡(80/65)≈72∘F\Delta T_{lm}=(80-65)/\ln(80/65)\approx72^\circ\mathrm F. With U=70 Btu/(h ft2 ∘F)U=70\ \mathrm{Btu/(h\,ft^2\,{}^\circ F)} and A=75 ft2A=75\ \mathrm{ft^2},

Q˙≈70×75×72=378,000 Btu/h.\dot Q\approx70\times75\times72=378{,}000\ \mathrm{Btu/h}.

The key is to choose the correct terminal differences before evaluating the logarithmic mean.

Interpreting a

Check the ends, not just the outlets

A means Tc,o>Th,oT_{c,o}>T_{h,o}. This does not, by itself, mean heat has reversed direction: the outlet temperatures are at opposite ends in counterflow, so compare the hot and cold temperatures at each actual end. Heat can still flow from hot to cold throughout if both counterflow terminal differences are positive:

Th,i−Tc,o>0,Th,o−Tc,i>0.T_{h,i}-T_{c,o}>0,\qquad T_{h,o}-T_{c,i}>0.

Illustrative hypothetical application: let the hot stream enter at 200 and leave at 110, while the cold stream enters at 70 and leaves at 130, all in the same temperature unit. Although 130>110130>110, the counterflow terminal differences are 200−130=70200-130=70 and 110−70=40110-70=40. Both are positive, so these outlet values do not imply a local reversal of the intended heat flow. A simple parallel-flow exchanger cannot sustain an outlet .

Correcting for Exchanger Configuration

Adjust the counterflow driving force

Multipass shell-and-tube and crossflow exchangers do not have a purely parallel- or counterflow temperature profile. For these configurations, first calculate the counterflow LMTD from the four stream temperatures, then apply the FF:

ΔTlm,corrected=FΔTlm,counterflow,Q˙=UAFΔTlm,counterflow.\Delta T_{lm,\mathrm{corrected}}=F\Delta T_{lm,\mathrm{counterflow}}, \qquad \dot Q=UA F\Delta T_{lm,\mathrm{counterflow}}.

The factor depends on exchanger configuration and temperature ratios; obtain it from the appropriate chart or a validated calculation method for that configuration. For ideal parallel- or counterflow double-pipe exchangers, F=1F=1. For many multipass and crossflow designs, F<1F<1, so the corrected driving force is smaller than the counterflow value. A small factor indicates a substantially reduced effective driving force and may mean that more heat-transfer area or a different arrangement is needed.

  • : The temperature difference between the hot and cold streams at one end of the exchanger.

  • : A logarithmic average of the two terminal temperature differences, used as the mean temperature driving force in the standard heat-transfer equation.