2 Refrigerant Pressures and Pressure-Temperature Charts
Learn how refrigerant pressure relates to saturation temperature, how to use pressure-temperature charts, and why operating pressures must be interpreted with system conditions and other measurements.
Pressure and
For a given refrigerant, pressure and are linked: higher pressure corresponds to higher , and lower pressure corresponds to lower . At saturation, liquid and vapor can coexist. While refrigerant is boiling or condensing, the is the temperature at which that phase change occurs at the measured pressure.
Using a
A relates saturation pressure and for a particular refrigerant. Identify the refrigerant first; never use another refrigerant’s chart column. Then find the measured pressure and read across to its corresponding , or begin with a temperature and read the corresponding pressure.
The relationship is refrigerant-specific. At a of , one Sporlan chart lists about for R-22, for R-410A, and for R-134a. These are saturation pressures at that temperature, not universal normal operating pressures for a system.
Pressure units and reference
Check the chart’s pressure units and reference before interpreting a reading. is measured relative to atmospheric pressure, whereas includes atmospheric pressure. Near sea level, the approximate relationship is:
The cited Sporlan chart reports psig at sea level. Do not compare values expressed in different pressure units without converting them.
in blends
Some refrigerant blends change temperature as they evaporate or condense at nearly constant pressure. This temperature change is called . Such blends can have distinct saturation values at the dew-point and bubble-point boundaries.
: the saturated-vapor boundary; use its saturation value when calculating .
: the saturated-liquid boundary; use its saturation value when calculating .
Use a chart or approved tool that identifies the correct dew- and bubble-point values for the refrigerant.
What operating pressures reflect
In a typical vapor-compression system, suction pressure reflects conditions around the evaporator, while discharge or condensing pressure reflects conditions around the condenser. The evaporator refrigerant must be cool enough to absorb heat, and the condenser refrigerant must be warm enough to reject heat.
Operating readings vary with refrigerant and system conditions, including indoor and outdoor temperatures, heating or cooling load, airflow, coil cleanliness, compressor operation, metering-device control, refrigerant charge, and pressure drop through the system. A change in any of these can shift operating pressures. Pressure at the compressor may also differ from pressure at a coil because refrigerant lines have pressure drop.
Interpreting readings
There is no single correct suction or discharge pressure for all systems, or for one system under every condition. Compare readings with the equipment manufacturer’s specifications and the actual operating conditions.
A describes saturation; by itself, it does not establish whether a system is correctly charged or operating properly. Compare a measured line temperature with its to determine or . Use the vapor for and the liquid for . Interpret pressure alongside line temperatures and relevant measurements such as and ; pressure alone is not a reliable diagnosis or charging method.