5 Refrigerant Practice and Review Free Online FlashCards

Study 5 Refrigerant Practice and Review with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

What do the letters A and B indicate in an ASHRAE refrigerant safety group?

Back

A indicates the lower-toxicity class; B indicates the higher-toxicity class.

02
Front

What should you remember about an A2L refrigerant?

Back

A2L is a flammable classification; for example, R-32 is A2L. A1 does not mean harmless.

03
Front

What does ozone-depletion potential (ODP) compare?

Back

Ozone-depletion potential compares a substance’s ozone-depletion impact with that of CFC-11.

04
Front

What is a key environmental and handling concern for CFCs such as R-12?

Back

CFCs such as R-12 deplete ozone. Do not release them; follow applicable recovery and disposal rules.

05
Front

How should you identify the refrigerant before service?

Back

Use the equipment nameplate and container label to match the exact refrigerant designation and suffix; cylinder color alone is not reliable identification.

06
Front

How do you confirm which refrigerant a unit is designed for?

Back

Confirm the exact refrigerant and approved charge from the nameplate or documentation. Similar pressure does not make another refrigerant an approved substitute.

07
Front

What must you check before reading a pressure–temperature chart?

Back

A P–T chart relates a refrigerant’s saturation temperature to its saturation pressure. Select the exact refrigerant’s chart and check whether pressures are psig or psia.

08
Front

At 40°F, how do the reference-chart pressures for R-410A and R-134a compare?

Back

At 40°F saturation temperature, the reference chart gives about 118.8 psig for R-410A and 35.0 psig for R-134a; these are not operating targets.

09
Front

Can a P–T chart reading alone confirm correct charge?

Back

No. A chart comparison alone cannot establish correct charge or diagnose a fault; interpret readings using operating conditions and the manufacturer’s diagnostic method.

10
Front

How should you use bubble-point and dew-point values for a refrigerant blend?

Back

Bubble-point and dew-point values represent different points for a blend that boils over a temperature range. Use the point specified by the manufacturer or service procedure.

11
Front

What should you do if a leak is suspected in a confined or poorly ventilated area?

Back

Leave the area and follow the site emergency procedure. Do not enter to investigate without authorization and appropriate controls.

12
Front

What key EPA Section 608 rules apply to covered refrigerant service?

Back

Do not intentionally vent covered refrigerants. Covered stationary-equipment service activities require certification, except apprentices may qualify for an exemption under close, continual supervision by a certified technician.