2 Safe Service of Low-Pressure Chillers Free Online FlashCards

Study 2 Safe Service of Low-Pressure Chillers with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

What can a leak draw into a low-pressure chiller?

Back

A leak in a below-atmospheric section can draw air and moisture into the system.

02
Front

What can unusually frequent purging indicate?

Back

Unusually frequent or prolonged purging can signal air infiltration, but it does not locate the leak.

03
Front

Which sites should be inspected for refrigerant leaks?

Back

Inspect likely sites such as gaskets, fittings, shaft seals, and heat-exchanger tubes with a suitable detector or approved locating method.

04
Front

How should pressure generally be raised for a charged-system leak check?

Back

Controlled heating, such as circulated warm water or a built-in heating device, is generally preferred. Use nitrogen only when the applicable procedure allows it.

05
Front

What limits must leak-test pressure stay within?

Back

Never exceed the pressure limit on the chiller nameplate or in its service manual; overpressure can damage components such as rupture discs.

06
Front

What refrigerant phases must be recovered?

Back

Recover liquid first when possible to speed recovery, then recover the remaining vapor. Removing liquid alone is not complete recovery.

07
Front

Why protect chiller water during evacuation?

Back

Follow the manufacturer’s directions to circulate or remove water. Excessive cooling during evacuation can freeze water in the tubes and damage the heat exchanger.

08
Front

Why heat chiller oil before removing it?

Back

When applicable, heat the oil to about 130°F before removal to reduce refrigerant release from the oil.

09
Front

What evacuation level does EPA’s table specify for low-pressure appliances?

Back

EPA’s table specifies 25 mm Hg absolute for low-pressure appliances when an evacuation level is required. Apply the current rules and equipment instructions for the specific repair.

10
Front

What can a pressure rise after evacuation indicate?

Back

A pressure rise can indicate remaining liquid refrigerant or refrigerant desorbing from oil.

11
Front

What pressure applies to a specified non-major-repair exception?

Back

For certain non-major repairs under specified conditions, a low-pressure appliance is brought to 0 psig before opening if it will not be evacuated to the atmosphere after service. Confirm the exact rule first.

12
Front

What work can qualify as a major repair?

Back

Major repairs include removing certain heat-exchange or compressor components, or opening a sufficiently large flow area for more than 15 minutes.