3 Evacuating Low-Pressure Systems Online Quiz Questions

Use this free practice quiz with 20 questions to review 3 Evacuating Low-Pressure Systems, test your knowledge, and prepare for your next test or exam.

20 questions
01
True or false
1 point

A conventional compound gauge can reliably measure the deep vacuum needed for chiller dehydration.

  1. A

    True

  2. B

    False

02
Choose one
1 point

During refrigerant removal from a low-pressure chiller, how should a technician protect the heat-exchanger water circuits?

  1. A

    Always drain every water circuit before refrigerant removal, regardless of the manufacturer’s procedure.

  2. B

    Maintain or remove water as the manufacturer specifies to prevent freezing in heat-exchanger tubes.

  3. C

    Leave water in the circuits and use compressed air to protect the tubes.

03
Choose all
1 point

Which choices are appropriate parts of a dehydration-evacuation setup? Select all that apply.

  1. A

    Use clean pump oil.

  2. B

    Use a conventional compound gauge as the instrument for measuring deep vacuum.

  3. C

    Use vacuum-rated, large-diameter hoses.

  4. D

    Use suitable isolation valves or a vacuum manifold.

04
Choose all
1 point

Why is it important to remove moisture from a low-pressure chiller? Select all supported effects.

  1. A

    It can freeze.

  2. B

    It can corrode components.

  3. C

    It guarantees that leaks will draw refrigerant out of a low-pressure system.

  4. D

    It can contribute to acid and sludge formation.

05
Choose one
1 point

Where should the micron gauge be placed during dehydration evacuation, and why?

  1. A

    At the vacuum pump, because the pump-side reading represents the chiller’s actual vacuum.

  2. B

    At the chiller, or as close to it as practical, because hose pressure drop can make the pump-side reading appear better than the system’s actual vacuum.

  3. C

    At the far end of the longest hose, because maximizing pressure drop improves measurement accuracy.

  4. D

    On a conventional compound gauge, because it reliably measures deep vacuum.

06
Written response
1 point

The listed EPA recovery evacuation level for low-pressure appliances is 25 mm Hg absolute. Express this level in microns.

07
Fill in the blank
1 point

Removing air and moisture after a system is sealed and leak-tested is ; removing refrigerant before the system is opened is .

08
Choose one
1 point

A valve is left closed between the pump and one section that requires evacuation. What is the likely consequence?

  1. A

    The vacuum pump will automatically evacuate the isolated section through the closed valve.

  2. B

    The isolated section will dry faster because it is protected from the pump.

  3. C

    The isolated section may remain undried because it is not connected to the pump.

  4. D

    The micron gauge will measure the isolated section’s pressure regardless of its location.

09
True or false
1 point

A standing vacuum test can help assess system tightness and dryness behavior, but it cannot by itself identify the location of a leak.

  1. A

    True

  2. B

    False

10
Written response
1 point

What instrument is used to measure absolute pressure during deep-vacuum evacuation?

11
Fill in the blank
1 point

In triple evacuation, the vacuum is broken with , and the process is repeated at .

12
Open ended
1 point

Describe how to perform and evaluate a standing-vacuum check after evacuating a chiller. Include the pump and gauge positions, what to observe, and what to do if the check fails.

13
True or false
1 point

When breaking a vacuum, dry nitrogen may be used as directed, but oxygen and compressed air must not be used.

  1. A

    True

  2. B

    False

14
Choose one
1 point

During dehydration, a pump-side reading suggests a deeper vacuum than expected at the chiller. Where should the micron gauge be placed to monitor the system’s actual vacuum most reliably?

  1. A

    Place the micron gauge beside the vacuum pump.

  2. B

    Place the micron gauge at the chiller, or as close to it as practical.

  3. C

    Use a compound gauge at the pump instead of a micron gauge.

  4. D

    Disconnect the gauge once the pump reaches its target.

15
Written response
1 point

For an EPA Section 608 refrigerant-recovery requirement, what absolute pressure, expressed in microns, is the listed evacuation level for a low-pressure appliance? Enter the numeric value in microns.

16
Choose one
1 point

A low-pressure system has been exposed to moisture during substantial repair, and the applicable procedure calls for the example triple-evacuation sequence described in the material. Which sequence matches that example?

  1. A

    Reach 500 microns, break the vacuum with oxygen, then stop without checking the system.

  2. B

    Pressurize with compressed air, evacuate once to 1,500 microns, and leave the pump connected.

  3. C

    Evacuate to 1,500 microns, isolate the pump and break the vacuum with dry nitrogen; repeat at 1,000 microns and then 500 microns, followed by a standing-vacuum check.

  4. D

    Evacuate to 1,000 microns, open the system to atmosphere, and finish at 1,500 microns.

17
Written response
1 point

What type of pressure does a micron gauge measure?

18
Choose one
1 point

During a standing-vacuum check, pressure rises slowly and continues to rise. Which set of causes is consistent with this behavior?

  1. A

    Moisture outgassing, refrigerant remaining in oil, or a leak.

  2. B

    A confirmed leak at the exact location of the gauge.

  3. C

    A normal result that proves the system is dry and leak-free.

  4. D

    A compound gauge converting the reading from absolute pressure.

19
Choose one
1 point

A technician must break a vacuum during a staged dehydration procedure. Which action is consistent with the material’s safety guidance?

  1. A

    Use oxygen because it contains no moisture, and pressurize until the system reaches atmospheric pressure.

  2. B

    Use compressed air at a pressure above the system’s allowable limit to speed the process.

  3. C

    Use any available gas if the pump is isolated first.

  4. D

    Use dry nitrogen safely according to equipment instructions, without exceeding the system’s allowable pressure.

20
Choose one
1 point

After leak testing, a technician discovers that a closed valve has isolated one section that must be dehydrated. What should be done before evacuation proceeds?

  1. A

    Leave the valve closed because the vacuum pump will evacuate the isolated section through the chiller walls.

  2. B

    Open or isolate valves as directed by the manufacturer so every section requiring evacuation is connected to the pump.

  3. C

    Close every valve and evacuate only the section nearest the pump.

  4. D

    Remove the micron gauge so the isolated section can equalize.