A conventional compound gauge can reliably measure the deep vacuum needed for chiller dehydration.
3 Evacuating Low-Pressure Systems Online Quiz Questions
Use this free practice quiz with 20 questions to review 3 Evacuating Low-Pressure Systems, test your knowledge, and prepare for your next test or exam.
During refrigerant removal from a low-pressure chiller, how should a technician protect the heat-exchanger water circuits?
- A
Always drain every water circuit before refrigerant removal, regardless of the manufacturer’s procedure.
- B
Maintain or remove water as the manufacturer specifies to prevent freezing in heat-exchanger tubes.
- C
Leave water in the circuits and use compressed air to protect the tubes.
Which choices are appropriate parts of a dehydration-evacuation setup? Select all that apply.
- A
Use clean pump oil.
- B
Use a conventional compound gauge as the instrument for measuring deep vacuum.
- C
Use vacuum-rated, large-diameter hoses.
- D
Use suitable isolation valves or a vacuum manifold.
Why is it important to remove moisture from a low-pressure chiller? Select all supported effects.
- A
It can freeze.
- B
It can corrode components.
- C
It guarantees that leaks will draw refrigerant out of a low-pressure system.
- D
It can contribute to acid and sludge formation.
Where should the micron gauge be placed during dehydration evacuation, and why?
- A
At the vacuum pump, because the pump-side reading represents the chiller’s actual vacuum.
- B
At the chiller, or as close to it as practical, because hose pressure drop can make the pump-side reading appear better than the system’s actual vacuum.
- C
At the far end of the longest hose, because maximizing pressure drop improves measurement accuracy.
- D
On a conventional compound gauge, because it reliably measures deep vacuum.
The listed EPA recovery evacuation level for low-pressure appliances is 25 mm Hg absolute. Express this level in microns.
Removing air and moisture after a system is sealed and leak-tested is ; removing refrigerant before the system is opened is .
A valve is left closed between the pump and one section that requires evacuation. What is the likely consequence?
- A
The vacuum pump will automatically evacuate the isolated section through the closed valve.
- B
The isolated section will dry faster because it is protected from the pump.
- C
The isolated section may remain undried because it is not connected to the pump.
- D
The micron gauge will measure the isolated section’s pressure regardless of its location.
A standing vacuum test can help assess system tightness and dryness behavior, but it cannot by itself identify the location of a leak.
- A
True
- B
False
What instrument is used to measure absolute pressure during deep-vacuum evacuation?
In triple evacuation, the vacuum is broken with , and the process is repeated at .
Describe how to perform and evaluate a standing-vacuum check after evacuating a chiller. Include the pump and gauge positions, what to observe, and what to do if the check fails.
When breaking a vacuum, dry nitrogen may be used as directed, but oxygen and compressed air must not be used.
- A
True
- B
False
During dehydration, a pump-side reading suggests a deeper vacuum than expected at the chiller. Where should the micron gauge be placed to monitor the system’s actual vacuum most reliably?
- A
Place the micron gauge beside the vacuum pump.
- B
Place the micron gauge at the chiller, or as close to it as practical.
- C
Use a compound gauge at the pump instead of a micron gauge.
- D
Disconnect the gauge once the pump reaches its target.
For an EPA Section 608 refrigerant-recovery requirement, what absolute pressure, expressed in microns, is the listed evacuation level for a low-pressure appliance? Enter the numeric value in microns.
A low-pressure system has been exposed to moisture during substantial repair, and the applicable procedure calls for the example triple-evacuation sequence described in the material. Which sequence matches that example?
- A
Reach 500 microns, break the vacuum with oxygen, then stop without checking the system.
- B
Pressurize with compressed air, evacuate once to 1,500 microns, and leave the pump connected.
- C
Evacuate to 1,500 microns, isolate the pump and break the vacuum with dry nitrogen; repeat at 1,000 microns and then 500 microns, followed by a standing-vacuum check.
- D
Evacuate to 1,000 microns, open the system to atmosphere, and finish at 1,500 microns.
What type of pressure does a micron gauge measure?
During a standing-vacuum check, pressure rises slowly and continues to rise. Which set of causes is consistent with this behavior?
- A
Moisture outgassing, refrigerant remaining in oil, or a leak.
- B
A confirmed leak at the exact location of the gauge.
- C
A normal result that proves the system is dry and leak-free.
- D
A compound gauge converting the reading from absolute pressure.
A technician must break a vacuum during a staged dehydration procedure. Which action is consistent with the material’s safety guidance?
- A
Use oxygen because it contains no moisture, and pressurize until the system reaches atmospheric pressure.
- B
Use compressed air at a pressure above the system’s allowable limit to speed the process.
- C
Use any available gas if the pump is isolated first.
- D
Use dry nitrogen safely according to equipment instructions, without exceeding the system’s allowable pressure.
After leak testing, a technician discovers that a closed valve has isolated one section that must be dehydrated. What should be done before evacuation proceeds?
- A
Leave the valve closed because the vacuum pump will evacuate the isolated section through the chiller walls.
- B
Open or isolate valves as directed by the manufacturer so every section requiring evacuation is connected to the pump.
- C
Close every valve and evacuate only the section nearest the pump.
- D
Remove the micron gauge so the isolated section can equalize.
Related study packs and tools
- Quiz
1 High- and Very-High-Pressure Refrigeration Systems
A medium-difficulty quiz on EPA pressure categories, refrigeration-cycle components, pressure behavior, and safety hazards.
EPA 608 Type IIUpdated - Quiz
2 Safe Service Preparation and Diagnostics
A medium-difficulty quiz on preparing for and performing safe initial diagnostics on high- and very-high-pressure refrigeration appliances.
EPA 608 Type IIUpdated - Quiz
3 Leak Detection, Repair, and Verification
A medium-difficulty quiz on locating refrigerant leaks, performing repairs safely, verifying system integrity, and applying relevant regulatory requirements.
EPA 608 Type IIUpdated - Quiz
4 Evacuation and Dehydration Procedures
A quiz on safe evacuation, dehydration, and vacuum verification for refrigeration circuits.
EPA 608 Type IIIUpdated - Quiz
4 Refrigerant Recovery and Cylinder Handling
A medium-difficulty quiz on safe refrigerant recovery, cylinder handling, and the differences among recovery, evacuation, and charging.
EPA 608 Type IIUpdated - Quiz
4 Small Appliance Refrigerant Recovery Procedures
A 14-question quiz on safe, compliant recovery procedures for small appliances, including equipment selection, recovery targets, and refrigerant handling.
EPA 608 Type IUpdated - Quiz
5 Appliance Servicing and Return to Service
A medium-difficulty quiz on diagnosing, repairing, testing, and documenting appliance service work before returning equipment to operation.
EPA 608 Type IIUpdated - Study guide
5 Appliance Servicing and Return to Service
A practical sequence for diagnosing, repairing, testing, and documenting refrigeration appliances before returning them to service.
EPA 608 Type IIUpdated - Quiz
5 Chiller Service Practice and Verification
Practice chiller recovery, safety checks, endpoint verification, and service documentation. Follow equipment-specific procedures and applicable requirements.
EPA 608 Type IIIUpdated - Study guide
5 Chiller Service Practice and Verification
A practical framework for safely recovering refrigerant from chillers, verifying recovery and dehydration endpoints, troubleshooting problems, and documenting service work.
EPA 608 Type IIIUpdated - Quiz
5 Small Appliance Service and Compliance Workflows
A medium-difficulty quiz on identifying small appliances and applying Section 608 service, recovery, leak-check, and disposal practices.
EPA 608 Type IUpdated - Quiz
6 Integrated Practice and Competency Checks
A medium-difficulty quiz on safe, compliant service decisions for stationary refrigeration and air-conditioning equipment.
EPA 608 Type IIUpdated