1 Low-Pressure Appliances and Chiller Fundamentals Online Quiz Questions

Use this free practice quiz with 20 questions to review 1 Low-Pressure Appliances and Chiller Fundamentals, test your knowledge, and prepare for your next test or exam.

20 questions
01
True or false
1 point

A refrigerant qualifies as low pressure under the stated EPA terminology when its boiling point is above 10°C (50°F) at standard atmospheric pressure. This classification does not mean every part of the operating system is always below atmospheric pressure. True or false?

  1. A

    True

  2. B

    False

02
Choose one
1 point

In a water-cooled chiller, which component transfers heat from the chilled-water loop to refrigerant that is boiling at low pressure?

  1. A

    Evaporator

  2. B

    Compressor

  3. C

    Expansion device

  4. D

    Purge unit

03
Choose one
1 point

Which chiller component meters liquid refrigerant into the evaporator and reduces its pressure?

  1. A

    Condenser

  2. B

    Compressor

  3. C

    Expansion device

  4. D

    Purge unit

04
Written response
1 point

A pressure gauge shows a vacuum. Relative to local atmospheric pressure, what is the system’s absolute pressure?

05
True or false
1 point

A leak develops in a part of a chiller operating below atmospheric pressure. Air and moisture may be drawn into the system rather than refrigerant simply being pushed outward. True or false?

  1. A

    True

  2. B

    False

06
Choose one
1 point

A technician is tracing the two water circuits of a typical water-cooled chiller. Which description correctly distinguishes their roles?

  1. A

    Chilled water carries rejected heat to the cooling tower, while condenser water carries cooling to the building.

  2. B

    Chilled water carries cooling to the building or process, while condenser water carries rejected heat to a heat sink.

  3. C

    Both circuits carry cooling to the building, but at different pressures.

  4. D

    Both circuits carry rejected heat from the refrigerant to the same heat sink.

07
Choose all
1 point

Air and moisture have entered a low-pressure chiller. Which effects are consistent with the described service conditions? Select all that apply.

  1. A

    Noncondensables can impair heat transfer.

  2. B

    Noncondensables can increase condenser pressure.

  3. C

    Moisture necessarily improves heat transfer and reduces condenser pressure.

  4. D

    Moisture can contribute to corrosion, contamination, or ice-related restrictions.

08
Written response
1 point

What absolute-pressure evacuation level does the EPA service-practice table specify for low-pressure appliances? Enter the value in mm Hg absolute.

09
Choose all
1 point

When investigating a possible system problem, which observations are identified as useful diagnostic clues? Select all that apply.

  1. A

    Purge-unit activity

  2. B

    The refrigerant’s original boiling point at standard atmospheric pressure

  3. C

    Pressure and temperature readings

  4. D

    Water temperatures and operating trends

  5. E

    A single clue that definitively identifies the leak location

10
Choose one
1 point

During refrigerant recovery from a chiller, why should a technician account for water remaining in the tubes?

  1. A

    Water in the tubes can raise the refrigerant’s boiling point during recovery.

  2. B

    Water in the tubes can prevent the compressor from raising vapor pressure.

  3. C

    Water in the tubes can freeze as refrigerant is removed and temperatures fall.

  4. D

    Water in the tubes guarantees that the purge unit will operate more frequently.

11
Choose one
1 point

A low-pressure chiller’s purge unit has been operating unusually frequently. What is the most appropriate interpretation?

  1. A

    It proves that refrigerant is leaking outward at the purge unit.

  2. B

    It can indicate air entering through a leak or another system problem.

  3. C

    It confirms that the evaporator pressure is above atmospheric pressure.

  4. D

    It shows that the expansion device is metering too much liquid refrigerant.

12
Open ended
1 point

Describe how refrigerant moves through a vapor-compression chiller cycle, explaining what happens to its pressure and temperature and how heat is transferred in each of the four main components.

13
Choose one
1 point

A refrigerant boils at 12°C (53.6°F) at standard atmospheric pressure. Based on the EPA definition, how should an appliance using this refrigerant be classified?

  1. A

    It uses a refrigerant that boils below 10°C (50°F) at standard atmospheric pressure.

  2. B

    It uses a refrigerant that boils above 10°C (50°F) at standard atmospheric pressure.

  3. C

    Every part of its operating system always remains below atmospheric pressure.

  4. D

    Its evaporator always operates above atmospheric pressure.

14
Choose one
1 point

Which action by the expansion device helps refrigerant enter the evaporator ready to boil at a low temperature?

  1. A

    It meters liquid refrigerant into the evaporator and lowers its pressure and saturation temperature.

  2. B

    It raises vapor pressure and temperature so the refrigerant can condense.

  3. C

    It removes air and other noncondensable gases from the system.

  4. D

    It transfers heat from the refrigerant to condenser water or air.

15
True or false
1 point

A pressure gauge shows a vacuum when the system’s absolute pressure is below local atmospheric pressure.

  1. A

    True

  2. B

    False

16
Choose one
1 point

A water-cooled chiller has separate chilled-water and condenser-water circuits. Which description correctly distinguishes their roles?

  1. A

    Both circuits carry cooling from the chiller to the building or process.

  2. B

    Chilled water carries rejected heat to a cooling tower, while condenser water supplies cooling to the building.

  3. C

    Chilled water carries cooling to the building or process, while condenser water carries rejected heat to a heat sink.

  4. D

    Condenser water supplies liquid refrigerant to the expansion device.

17
Written response
1 point

What evacuation level, in mm Hg absolute, does EPA’s service-practice table specify for low-pressure appliances? Enter the numerical value only.

18
Written response
1 point

What specific possible cause can unusually frequent purge-unit operation indicate in a low-pressure chiller?

19
Fill in the blank
1 point

For a given refrigerant, a technician lowers its pressure. According to the pressure–temperature relationship, the refrigerant’s boiling temperature .

20
Fill in the blank
1 point

A technician needs to compare a measured pressure with the saturation temperature for a specific refrigerant. The technician should consult the correct refrigerant or its digital equivalent.