2 Safe Service of Low-Pressure Chillers Online Quiz Questions

Use this free practice quiz with 20 questions to review 2 Safe Service of Low-Pressure Chillers, test your knowledge, and prepare for your next test or exam.

20 questions
01
True or false
1 point

True or false: A leak in a below-atmospheric section of a low-pressure chiller can draw air and moisture into the refrigerant circuit.

  1. A

    True

  2. B

    False

02
Choose one
1 point

A charged low-pressure chiller needs a leak check that requires raising system pressure. Which approach is generally preferred?

  1. A

    Pressurize the system with compressed air until the leak becomes audible.

  2. B

    Use controlled heating, following the applicable procedure and pressure limits.

  3. C

    Raise pressure without monitoring it, then inspect only the rupture disc.

  4. D

    Use nitrogen for every leak check, regardless of the applicable procedure.

03
Choose one
1 point

A technician is reviewing the function of a low-pressure chiller's purge unit. What does the unit remove from the system?

  1. A

    It removes liquid refrigerant to speed up recovery.

  2. B

    It prevents water-side tubes from freezing during evacuation.

  3. C

    It removes noncondensable gases from the system.

  4. D

    It measures whether a leak is located at a heat-exchanger tube.

04
Fill in the blank
1 point

When applicable, EPA Type III guidance calls for heating oil to about before removal to reduce refrigerant release from the oil.

05
Choose all
1 point

Select all actions that follow the material's safety guidance for preparing for service and responding to a suspected significant refrigerant leak.

  1. A

    Identify the refrigerant and review site emergency procedures before work.

  2. B

    Enter a space after a release to check whether it is safe before calling for help.

  3. C

    If an alarm sounds or a significant leak is suspected, leave, alert others, and follow the evacuation plan.

  4. D

    Attempt an unprotected rescue if someone may be in the affected area.

06
Choose one
1 point

When recovering refrigerant from a chiller, which sequence is recommended when liquid recovery is possible?

  1. A

    Recover liquid only; vapor recovery is unnecessary once the liquid is removed.

  2. B

    Recover liquid first when possible, then recover the remaining vapor.

  3. C

    Release the vapor before recovering the liquid.

  4. D

    Recover vapor first and leave liquid in the chiller for the repair.

07
True or false
1 point

True or false: During evacuation, excessive cooling can freeze water in a chiller's tubes and damage the heat exchanger.

  1. A

    True

  2. B

    False

08
Written response
1 point

For a suspected water-side tube leak, the manufacturer's procedure should guide isolation and inspection of which chiller component?

09
Fill in the blank
1 point

After reaching the required evacuation level, a pressure rise during the wait may indicate .

10
Written response
1 point

When an EPA evacuation level is required, what value in mm Hg absolute does the table specify for a low-pressure appliance?

11
Choose all
1 point

Select all actions that the material identifies as meeting a part of EPA's definition of a major repair.

  1. A

    Removing certain heat-exchange or compressor components.

  2. B

    Replacing a service label without opening the appliance.

  3. C

    Opening a sufficiently large flow area for more than 15 minutes.

  4. D

    Inspecting a gasket externally without opening the appliance.

12
Choose one
1 point

A technician is considering EPA's alternative procedure for opening a low-pressure appliance. Which situation matches the material's stated conditions for considering it?

  1. A

    For every repair, regardless of scope, open the appliance while it is under vacuum.

  2. B

    Use the alternative whenever the appliance has a purge unit, even if it will be evacuated to the atmosphere after service.

  3. C

    For a qualifying non-major repair when the appliance will not be evacuated to the atmosphere after service, follow the specified procedure to bring it to 0 psig before opening.

  4. D

    Bring the appliance to any pressure below its nameplate limit; no further conditions apply.

13
Open ended
1 point

A low-pressure chiller has unusually frequent purge operation and recurring moisture. Explain what these clues may indicate, why they are not enough to locate the leak, and how a technician should proceed to identify its location.

14
True or false
1 point

True or false: Unusually frequent or prolonged purge operation in a low-pressure chiller identifies the exact location of a leak.

  1. A

    True

  2. B

    False

15
Choose one
1 point

During evacuation of a chiller that contains water in its tubes, why should water be circulated or removed as directed by the manufacturer?

  1. A

    It helps locate refrigerant leaks in the water box.

  2. B

    It helps prevent water in the tubes from freezing and damaging the heat exchanger.

  3. C

    It ensures all refrigerant leaves the oil without heating.

  4. D

    It allows the system to be opened without checking recovery requirements.

16
Choose one
1 point

A low-pressure chiller’s purge unit begins operating unusually often. What is the most appropriate interpretation of this clue?

  1. A

    It proves that the leak is at the purge unit.

  2. B

    It confirms that refrigerant is escaping from an above-atmospheric section.

  3. C

    It can signal air infiltration, but does not identify the leak location.

  4. D

    It shows that the system has reached its required evacuation level.

17
Choose one
1 point

A technician needs to raise pressure on a charged low-pressure chiller for a leak check. Which approach follows the general guidance?

  1. A

    Use controlled heating, and stay within the chiller’s pressure limit.

  2. B

    Pressurize with nitrogen in every case, up to the pressure needed to find the leak.

  3. C

    Raise pressure until the purge unit stops operating.

  4. D

    Use any pressure that does not exceed the recovery cylinder’s rating.

18
Written response
1 point

When applicable, to about what temperature should oil be heated before removal to reduce refrigerant release from the oil? Enter the value in °F.

19
Written response
1 point

After a chiller reaches its required evacuation level, pressure rises during the wait-and-check period. Name either of the two possible causes identified in the service guidance.

20
Choose one
1 point

Which statement correctly describes using nitrogen to raise pressure during a leak check on a low-pressure chiller?

  1. A

    Nitrogen may always be used, provided the chiller is below atmospheric pressure.

  2. B

    Nitrogen may be used only when the applicable procedure allows it.

  3. C

    Nitrogen is required for every leak check on a low-pressure chiller.

  4. D

    Nitrogen may be used without regard to the chiller’s pressure limit.