How do refrigerant recovery and dehydration evacuation differ?

Back

Refrigerant recovery removes refrigerant before the system is opened; dehydration evacuation removes air and moisture after the system is sealed and leak-tested.

02
Front

Why can leaks draw air into a low-pressure chiller?

Back

Because low-pressure chillers can operate below atmospheric pressure, leaks may draw air and moisture into the system.

03
Front

What damage can moisture cause inside a chiller?

Back

Moisture can freeze, corrode components, or contribute to acid and sludge formation.

04
Front

How does a vacuum help dehydrate a chiller, and what can slow drying?

Back

A vacuum lowers water’s boiling point so moisture can vaporize and be removed. Pooled water, cold surfaces, oil, and moisture trapped in materials can make drying slow.

05
Front

Where should the micron gauge be placed during evacuation?

Back

Place the micron gauge at the chiller, or as close to it as practical, so it measures the system’s actual vacuum rather than a potentially better reading at the pump.

06
Front

Why is a compound gauge unsuitable for measuring deep vacuum?

Back

A conventional compound gauge cannot reliably measure deep vacuum; use an electronic micron gauge.

07
Front

What must be completed before dehydration evacuation?

Back

Recover the refrigerant and complete the required leak test before dehydration evacuation.

08
Front

Why must the valves connect all sections requiring evacuation?

Back

Connect all sections requiring evacuation to the pump as directed. A closed valve can leave part of the system undried.

09
Front

What is the basic sequence of a triple evacuation?

Back

Triple evacuation means evacuating to an intermediate vacuum, isolating the pump, breaking the vacuum with dry nitrogen, and repeating at progressively lower pressures. One example uses 1,500, then 1,000, then 500 microns; these are not universal targets.

10
Front

What gases must not be used to break a vacuum?

Back

Use dry nitrogen safely and follow equipment instructions. Never use oxygen or compressed air to break a vacuum, and never exceed allowable system pressure.

11
Front

What does a micron gauge measure, and what indicates a deeper vacuum?

Back

A micron is one-millionth of a meter of mercury pressure. The micron gauge measures absolute pressure, and lower absolute pressure means a deeper vacuum.

12
Front

How is a standing-vacuum check performed?

Back

Reach the specified final vacuum, close the isolation valve between the chiller and pump, keep the gauge sensing the chiller, and observe pressure rise over the specified hold period.