How should you identify the refrigerant before recovery?

Back

Identify the refrigerant and charge from the appliance nameplate and service records; never mix refrigerants.

02
Front

What recovery equipment is required for applicable stationary appliances?

Back

Use recovery equipment rated for the appliance and refrigerant. Section 608 technicians must use certified recovery equipment for applicable stationary appliances.

03
Front

Why manage the chiller’s water side during evacuation?

Back

Manage the water side as directed by the manufacturer; circulating or removing water during evacuation can reduce the risk of freezing chiller tubes.

04
Front

What makes a recovery cylinder suitable for a refrigerant?

Back

Use a recovery cylinder approved for the refrigerant and rated for its pressure.

05
Front

What should you check when setting up the recovery circuit?

Back

Connect suitable hoses and the manifold or recovery unit to the chiller’s liquid and vapor service connections. Check hoses, fittings, and valves for leaks.

06
Front

How should hoses be cleared without releasing refrigerant?

Back

Clear or evacuate hoses using the equipment’s approved procedure; do not vent refrigerant.

07
Front

Why is liquid generally recovered before vapor?

Back

Recover bulk liquid first because a given volume of liquid contains much more refrigerant by mass than the same volume of vapor.

08
Front

When may a push-pull method be used?

Back

A push-pull method can transfer bulk liquid quickly when the system layout and equipment permit it; use only the manufacturer-specified valve arrangement.

09
Front

What must you prevent when using a recovery unit?

Back

Do not allow liquid refrigerant to enter a recovery unit that is not designed to handle liquid.

10
Front

What is recovered after bulk liquid has been removed?

Back

After bulk liquid is removed, recover the remaining vapor through the appropriate vapor connection.

11
Front

What must be suitable for low-pressure chiller recovery?

Back

For a low-pressure chiller, the recovery device’s high-pressure cut-out and other controls must be suitable for low-pressure service.

12
Front

What evacuation level applies to low-pressure appliances?

Back

The required evacuation level for low-pressure appliances is 25 mm Hg25\ \mathrm{mm\ Hg} absolute, not a gauge-vacuum reading.