When is EPA Section 608 certification generally needed?

Back

Technicians who may violate the integrity of a refrigerant circuit generally need EPA Section 608 certification.

02
Front

What must happen before opening an appliance with more than 5 pounds of refrigerant?

Back

For appliances with more than 5 pounds of refrigerant, recover to the applicable EPA evacuation level before opening the appliance or isolated section.

03
Front

How should technicians prevent refrigerant mixing during recovery?

Back

Use recovery equipment suitable for the refrigerant and appliance, along with a compatible recovery cylinder. Do not mix refrigerants.

04
Front

What evacuation target does the table list for high-pressure equipment charged with less than 200 pounds?

Back

The table lists 0 inches Hg vacuum for high-pressure appliances or isolated components charged with less than 200 pounds, regardless of whether they were made before or after November 15, 1993.

05
Front

What evacuation target does the table list for very-high-pressure appliances?

Back

The table lists 0 inches Hg vacuum for very-high-pressure appliances.

06
Front

What limits apply when a leak prevents the normal evacuation level?

Back

Where possible, isolate leaking from non-leaking components. Evacuate non-leaking sections to their applicable level; the leaking section must reach the lowest achievable level without remaining above 0 psig.

07
Front

Which gases must not be used to pressure-test a refrigeration circuit?

Back

Do not use oxygen or compressed air to pressure-test a refrigeration circuit. Use regulated dry nitrogen only when the approved procedure permits it.

08
Front

When is recovered refrigerant generally subject to reclamation before reuse?

Back

Recovered refrigerant may generally be returned to the same appliance or another appliance owned by the same person. If ownership changes, an EPA-certified reclaimer is generally required.

09
Front

What pressure restriction applies when changing oil that may contain refrigerant?

Back

EPA prohibits changing oil above 5 psig, so refrigerant contained in the oil must be considered.

10
Front

Which appliances may be covered by Section 608 leak-repair requirements?

Back

Section 608 leak-repair requirements apply to appliances with a full charge of 50 pounds or more of an ozone-depleting refrigerant when the applicable leak-rate trigger is exceeded.

11
Front

What leak-rate triggers are listed for Section 608 appliances?

Back

The triggers are 30% for industrial process refrigeration, 20% for commercial refrigeration, and 10% for comfort cooling and other appliances.

12
Front

What is the general AIM Act ER&R leak-repair deadline?

Back

The general repair deadline is 30 days from the relevant refrigerant addition, or 120 days when an industrial process shutdown is required. Verification, inspections, records, and exceptions also apply.