5 Appliance Servicing and Return to Service Free Online FlashCards

Study 5 Appliance Servicing and Return to Service with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

What sequence guides a reliable appliance service visit?

Back

Identify, assess, isolate, recover as required, repair, test, restore, verify, and record.

02
Front

What should be inspected before disturbing the refrigerant circuit?

Back

Inspect controls, electrical connections, airflow or water flow, heat exchangers, piping, and visible signs of oil or refrigerant leakage.

03
Front

What can a pressure or vacuum decay check establish about a suspected leak?

Back

A pressure or vacuum decay check may show that a loss exists, but it does not necessarily locate the leak.

04
Front

What are two core requirements when isolating a circuit for refrigerant recovery?

Back

Isolate the relevant circuit using the manufacturer’s procedure. Do not intentionally vent refrigerant.

05
Front

How does the recovery endpoint differ from the post-repair evacuation vacuum?

Back

The EPA recovery endpoint for opening an appliance differs from the deeper vacuum later used to remove air and moisture from a repaired circuit.

06
Front

How should refrigerant be recovered when a leak prevents the required recovery level?

Back

Recover non-leaking portions to the applicable level. Recover the leaking portion to the lowest attainable pressure without substantial contamination, and do not exceed 0 psig for that portion.

07
Front

Which gases must never be used to pressurize a refrigerant circuit?

Back

Never use oxygen or compressed air to pressurize a refrigerant circuit.

08
Front

When is the initial leak verification test performed under applicable EPA rules?

Back

For appliances subject to applicable EPA leak-repair rules, perform the required initial verification test after repair and before adding refrigerant.

09
Front

Why is a repaired refrigerant circuit evacuated before charging?

Back

Evacuate the repaired circuit according to manufacturer specifications to remove air and moisture.

10
Front

What must be controlled and documented when charging an appliance?

Back

Use the correct refrigerant and specified amount and method, and record the quantity added.

11
Front

What should be checked during appliance startup?

Back

Check for leaks, abnormal noise or vibration, and correct control response. Compare relevant pressures, temperatures, superheat or subcooling, and capacity indicators with manufacturer specifications.

12
Front

What conditions must be met before an appliance is returned to service?

Back

Return it only after the fault is corrected, required leak verification is complete, the circuit is properly evacuated and charged, and operation is confirmed under normal conditions.