01
Front

What does refrigerant recovery do?

Back

Recovery transfers refrigerant from an appliance into an external container; it does not require cleaning or testing the refrigerant.

02
Front

What does EPA Section 608 generally prohibit during service?

Back

Intentional venting during service is generally prohibited under EPA Section 608.

03
Front

What must recovery equipment be compatible with?

Back

Use a recovery machine, hoses, fittings, and cylinder that are compatible with the refrigerant and its pressure.

04
Front

What extra precaution applies when recovering flammable refrigerants?

Back

Use equipment specifically approved for that refrigerant and follow its additional safety requirements.

05
Front

Can a vacuum pump be used to recover refrigerant?

Back

Do not use a vacuum pump to recover refrigerant. A vacuum pump is used for evacuation after refrigerant has been recovered.

06
Front

What kind of cylinder should be used for recovery?

Back

Use an authorized, refillable recovery cylinder—not a disposable charging cylinder.

07
Front

What should be checked before using a recovery cylinder?

Back

Verify that the cylinder’s pressure rating and condition are suitable. Do not use one with damage, a faulty valve, or an expired requalification.

08
Front

How should different refrigerants be stored during recovery?

Back

Keep different refrigerants separate and use a dedicated, clearly identified cylinder for each refrigerant.

09
Front

How should a recovery cylinder’s fill be monitored?

Back

Put the cylinder on a scale before recovery and control the fill by weight. Do not rely on pressure alone to estimate how full it is.

10
Front

Does the common 80% liquid-volume limit always determine cylinder fill?

Back

A common training limit is 80% liquid volume, but the applicable cylinder and refrigerant limits control.

11
Front

What should you do if the recovery cylinder reaches its limit?

Back

Stop recovery if the cylinder reaches its limit, and do not bypass an overfill shutoff.

12
Front

How does evacuation differ from recovery?

Back

Recovery transfers refrigerant into an external cylinder; evacuation removes air, moisture, and other noncondensables from the appliance after recovery.