4 Evacuation and Dehydration Procedures Free Online FlashCards

Study 4 Evacuation and Dehydration Procedures with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

How do evacuation and dehydration differ?

Back

Evacuation removes refrigerant, air, and other gases; dehydration removes water vapor and moisture from the circuit.

02
Front

Does a deep vacuum replace refrigerant recovery or leak testing?

Back

No. A deep vacuum can help dry the system, but it does not replace refrigerant recovery or a leak test.

03
Front

What must be done before opening the refrigeration circuit?

Back

Recover refrigerant with approved equipment before opening the circuit. Do not vent refrigerant.

04
Front

What low-pressure recovery level does EPA Section 608 list for qualifying appliances?

Back

For U.S. stationary appliances with more than five pounds of refrigerant, the listed recovery level for a low-pressure appliance is 25 mm Hg absolute. This is not a deep-dehydration target.

05
Front

Where should the micron gauge be placed?

Back

Use a calibrated micron gauge at the chiller or as close to the system as practical, not at the pump. Hose restriction can make the pump-side reading look better than the system vacuum.

06
Front

Why pressure-test for leaks before dehydration?

Back

Repair leaks and complete the required pressure leak test before dehydration; a leak can prevent a reliable vacuum.

07
Front

Why can moisture freeze during evacuation?

Back

As pressure falls, water boils at lower temperatures. Evaporation can cool moisture until it freezes, temporarily slowing drying and making readings misleading.

08
Front

How is a vacuum-decay test started?

Back

Close the valve between the system and pump to isolate the chiller, then stop or isolate the pump as directed. Record the starting micron reading, time, and system temperature.

09
Front

What can a rising pressure during a vacuum-decay test indicate?

Back

A rise toward atmospheric pressure suggests a leak; a rise that slows or stabilizes below atmospheric pressure can be consistent with moisture boiling off. A decay test alone cannot conclusively distinguish them.

10
Front

What gases are prohibited or restricted for pressure testing?

Back

Never pressure-test with oxygen or compressed air. Use dry nitrogen only with a regulator and within the manufacturer's pressure limits.

11
Front

How should standing water be removed before evacuation?

Back

Remove standing water using the manufacturer's procedure; a vacuum pump is not a substitute for draining bulk liquid.

12
Front

Can a conventional manifold gauge verify a deep vacuum?

Back

No. A conventional manifold gauge is not accurate enough to verify a deep vacuum.