What qualifies as a small appliance?

Back

A factory-made, factory-charged, hermetically sealed appliance containing 5 lb (2.3 kg) or less of refrigerant.

02
Front

What certification is generally required to service a small appliance?

Back

Technicians servicing or repairing small appliances generally need EPA Section 608 Type I or Universal certification. Recovery solely to prepare an appliance for disposal is an exception, but compliant equipment is still required.

03
Front

When does the 80% recovery requirement apply?

Back

Recover at least 80% when using equipment manufactured before November 15, 1993, or when the appliance compressor is not functional.

04
Front

When does the 90% recovery requirement apply?

Back

Recover at least 90% when using equipment manufactured after November 15, 1993, and the appliance compressor is functional.

05
Front

What vacuum endpoint is an alternative to the recovery percentage?

Back

The small-appliance rule also allows evacuation to 4 in. Hg vacuum as an alternative to the specified recovery percentage.

06
Front

What should you check on the appliance before connecting equipment?

Back

Read the nameplate to identify the refrigerant, charge, and any flammability warning before connecting recovery equipment.

07
Front

What precautions are needed for a flammable refrigerant?

Back

Use recovery equipment and cylinders specifically suitable for that refrigerant, control ignition sources, and follow the equipment manufacturer’s safety instructions.

08
Front

Why must different refrigerants be kept separate?

Back

Keep different refrigerants separate. Mixing can contaminate the recovered material and make it difficult or impossible to reclaim.

09
Front

How should cylinder filling be monitored?

Back

Use a scale to monitor the transferred refrigerant and stop before the cylinder reaches its marked maximum filling weight. Do not estimate fullness from pressure alone.

10
Front

What does refrigerant recovery do?

Back

Recovery removes refrigerant and stores it in an external container; it does not by itself clean or purify the refrigerant.

11
Front

What must you never do with a hermetic compressor under vacuum?

Back

Do not energize a hermetic compressor while the system is under vacuum.

12
Front

What can pressure rebound after recovery indicate?

Back

After reaching the target, wait briefly and recheck pressure. A pressure rise can indicate refrigerant remaining in the system or oil, so continue recovery as appropriate.