What qualifies as a small appliance under Section 608?

Back

A small appliance is factory-manufactured, charged, and hermetically sealed, with five pounds or less of refrigerant.

02
Front

Which Section 608 certification covers small-appliance service?

Back

Type I certification covers servicing small appliances.

03
Front

What kind of small-appliance work requires Section 608 certification?

Back

Work that could open or compromise the refrigerant circuit, including connecting gauges or adding or removing refrigerant, requires the appropriate Section 608 certification.

04
Front

What should you confirm before beginning appliance service?

Back

Read the nameplate and service information to confirm the refrigerant type, factory charge, and whether the appliance meets the small-appliance definition.

05
Front

What should be checked before blaming a sealed-system fault?

Back

Check accessible causes such as power, controls, airflow, condenser cleanliness, and door seals before concluding that the sealed system is at fault.

06
Front

May technicians intentionally vent refrigerant during service?

Back

Intentional refrigerant release during servicing, repair, or disposal is prohibited under Section 608.

07
Front

What recovery benchmark applies when the compressor works?

Back

The general benchmark is 90 percent when the compressor works and qualifying recovery equipment manufactured after November 15, 1993, is used.

08
Front

What evacuation alternative does EPA state for small-appliance recovery?

Back

Evacuating the appliance to 4 inches of mercury vacuum is an alternative stated by EPA; follow the recovery-equipment manufacturer's instructions.

09
Front

What must happen before opening a small appliance's refrigerant circuit?

Back

Use recovery equipment certified for the intended application and recover refrigerant before opening the circuit.

10
Front

How should a repaired refrigerant circuit be leak-checked?

Back

After repair, check repaired areas and disturbed joints with a method suitable for the refrigerant and appliance. A leak check does not replace required recovery.

11
Front

What full-charge threshold triggers EPA's leak-repair program?

Back

EPA's Section 608 leak-repair program for ozone-depleting refrigerant applies to appliances with a full charge of 50 pounds or more; it is not the ordinary leak-repair rule for qualifying small appliances.

12
Front

What information belongs in a clear small-appliance service record?

Back

Record the appliance identifier, refrigerant and nameplate charge, complaint, diagnosis, work performed, leak-check method and result, refrigerant recovered or added, and operating checks.