01
Front

What confirms that refrigerant recovery is complete?

Back

Confirm the required evacuation level at the appliance, ensure refrigerant is safely contained, and leave equipment and records in a known condition. Elapsed time or low recovery-machine inlet pressure alone does not prove completion.

02
Front

What does a reading of 0 psig mean?

Back

A reading of 0 psig is atmospheric pressure, not a vacuum.

03
Front

How does the charge affect the evacuation level for medium-pressure appliances?

Back

Under 200 lb requires 10 in. Hg vacuum; 200 lb or more requires 15 in. Hg vacuum.

04
Front

What evacuation level applies to a low-pressure appliance?

Back

The required level is 25 mm Hg absolute.

05
Front

What can pressure rebound after recovery indicate?

Back

A pressure rise can mean refrigerant is boiling out of oil or migrating from another section. Continue recovery as appropriate and verify the required level again before opening the circuit.

06
Front

What is the recovery approach when a leak prevents reaching the normal evacuation level?

Back

Where possible, isolate leaking from non-leaking components. Evacuate non-leaking portions to the required level and leaking portions to the lowest attainable level that does not substantially contaminate recovered refrigerant, not exceeding 0 psig.

07
Front

How should a recovery cylinder’s fill be controlled?

Back

Use a compatible, serviceable recovery cylinder and weigh it during and after recovery. Do not exceed its marked filling limit or maximum gross weight.

08
Front

Why should different refrigerants not be combined in one cylinder?

Back

Keep different refrigerants separate. Mixing can make them difficult or impossible to reuse and may require specialized handling.

09
Front

What does refrigerant recycling mean?

Back

Recycling cleans refrigerant for reuse in equipment owned by the same person.

10
Front

What must happen before recovered refrigerant is resold after changing ownership?

Back

If recovered refrigerant changes ownership, it must be reclaimed by an EPA-certified reclaimer before resale.

11
Front

What should you check if recovery is unusually slow or stops early?

Back

Check valve positions, hoses and filters, machine airflow, power supply, and whether the cylinder is full or overheated. Follow manufacturer instructions; do not bypass safety devices.

12
Front

How should unexpectedly high cylinder pressure be handled?

Back

Consider cylinder temperature and refrigerant identity, and let the cylinder stabilize before interpreting pressure. Do not vent refrigerant; stop handling a potentially overfilled, leaking, or unsafe cylinder and follow applicable procedures.