3 Refrigerant Recovery Procedures Online Quiz Questions

Use this free practice quiz with 20 questions to review 3 Refrigerant Recovery Procedures, test your knowledge, and prepare for your next test or exam.

20 questions
01
True or false
1 point

During stationary air-conditioning service in the United States, it is acceptable to intentionally vent refrigerant if recovery would take too long.

  1. A

    True

  2. B

    False

02
Choose one
1 point

A technician is recovering refrigerant into an approved cylinder. Which practice best prevents overfilling?

  1. A

    Fill the cylinder to its marked limit, then add a small amount to allow for later settling.

  2. B

    Weigh the cylinder during recovery and stop before it reaches its marked fill limit.

  3. C

    Estimate the amount by recovery time and check the cylinder weight only after the job.

  4. D

    Continue filling until the cylinder pressure matches the system pressure.

03
Written response
1 point

What recovery method removes refrigerant as a gas to clear the charge remaining after accessible liquid has been recovered?

04
Fill in the blank
1 point

For a burned-out compressor or contaminated refrigerant, collect the refrigerant in a clearly identified and do not combine it with clean refrigerant.

05
Choose one
1 point

Liquid entering a recovery machine too rapidly causes knocking. What should the operator do?

  1. A

    Increase inlet flow so the machine clears the liquid faster.

  2. B

    Switch off the machine and leave the valves open.

  3. C

    Throttle the inlet as the machine manual directs.

  4. D

    Vent a small amount of refrigerant to reduce the inlet pressure.

06
True or false
1 point

Recovering refrigerant from an appliance does not necessarily clean or purify the refrigerant.

  1. A

    True

  2. B

    False

07
Choose all
1 point

Which setup practices are appropriate for refrigerant recovery? Select all that apply.

  1. A

    Use a recovery machine approved for the refrigerant being handled.

  2. B

    Use one cylinder for different refrigerants if it is weighed carefully.

  3. C

    Use a separate, properly identified cylinder for each refrigerant.

  4. D

    Monitor the cylinder weight throughout recovery.

  5. E

    Use the same hose and cylinder-port arrangement for every recovery machine.

08
Fill in the blank
1 point

After the required level is reached, the system valves are closed as directed and pressure is allowed to stabilize. A pressure rise may indicate refrigerant remains in or .

09
Written response
1 point

Under the stated EPA leak exception, leaking sections must be brought to the lowest attainable pressure, not above what pressure? Enter the value in psig.

10
Choose one
1 point

A technician is handling a low-pressure appliance during a non-major repair that will not be followed by evacuation to the atmosphere. Under the specific EPA rule described, what must happen before the appliance is opened?

  1. A

    Open the appliance directly because low-pressure systems do not require recovery.

  2. B

    For the specified repair situation, pressurize the appliance to 0 psig before opening it.

  3. C

    Pressurize the appliance to 0 psig only after opening it.

  4. D

    Use the push-pull method in every case, regardless of the appliance or repair.

11
Choose all
1 point

Which statements correctly describe liquid push-pull recovery? Select all that apply.

  1. A

    It transfers accessible bulk liquid using pressure and a siphon effect.

  2. B

    It is suitable for every system and removes all remaining vapor.

  3. C

    It requires an appropriate system layout and enough accessible liquid.

  4. D

    A siphon can continue after the machine is switched off, so valves must be closed as directed.

  5. E

    It eliminates the need to monitor cylinder weight.

12
Choose one
1 point

An appliance contains 200 lb of refrigerant and is classified as medium-pressure. The recovery equipment was manufactured on or after November 15, 1993. What evacuation level applies?

  1. A

    4 in. Hg vacuum

  2. B

    15 in. Hg vacuum

  3. C

    25 mm Hg absolute

  4. D

    0 in. Hg vacuum

13
Open ended
1 point

Describe a safe recovery sequence for a normally charged system when accessible liquid can be recovered. Include how the technician should handle the remaining charge and verify completion.

14
Choose one
1 point

After recovering accessible liquid from a system, which method is used to remove the remaining refrigerant as gas?

  1. A

    Use liquid push-pull to remove all refrigerant, including the remaining vapor.

  2. B

    Use vapor recovery to remove the remaining refrigerant as gas.

  3. C

    Stop recovery once accessible liquid has been transferred.

  4. D

    Open the appliance after switching off the recovery machine.

15
Choose one
1 point

A technician must recover two different refrigerants. Which cylinder practice is appropriate?

  1. A

    Use one cylinder for all refrigerants if it is large enough.

  2. B

    Mix refrigerants only when both are clean.

  3. C

    Use a separate, properly identified cylinder for each refrigerant.

  4. D

    Use an unmarked cylinder if the refrigerant is later tested.

16
True or false
1 point

Liquid push-pull transfers accessible bulk liquid, but it does not remove the refrigerant vapor that remains in the system.

  1. A

    True

  2. B

    False

17
Choose one
1 point

During recovery, liquid entering the machine causes knocking. What should the technician do?

  1. A

    Throttle the inlet as the machine manual directs.

  2. B

    Increase liquid flow so the machine clears it faster.

  3. C

    Close all valves and leave liquid trapped between them.

  4. D

    Switch off the machine but leave the liquid path open.

18
Choose one
1 point

How should a technician manage cylinder filling during refrigerant recovery?

  1. A

    Estimate the amount transferred from the machine's run time.

  2. B

    Stop weighing the cylinder once liquid transfer begins.

  3. C

    Fill the cylinder to its marked limit, then allow it to warm.

  4. D

    Monitor cylinder weight and stop before its marked fill limit.

19
Written response
1 point

An appliance contains 250 lb of refrigerant and is in the high-pressure category. What evacuation level applies when the recovery equipment was manufactured on or after November 15, 1993?

20
Written response
1 point

For a low-pressure appliance undergoing a qualifying non-major repair that is not followed by evacuation to the atmosphere, to what pressure must it be pressurized before opening?