01
Front

What does refrigerant recovery do?

Back

Recovery removes refrigerant from an appliance and stores it in an external container; it does not necessarily clean or purify the refrigerant.

02
Front

What does Section 608 prohibit during stationary-system service?

Back

Section 608 prohibits intentional venting during stationary air-conditioning and refrigeration service in the United States.

03
Front

What must guide the choice and use of recovery equipment?

Back

Use equipment approved for the refrigerant, and follow the recovery-machine manufacturer’s instructions and applicable regulations.

04
Front

How should cylinders be assigned when recovering different refrigerants?

Back

Use a separate, properly identified cylinder for each refrigerant; do not mix refrigerants.

05
Front

What should you do if liquid entering the recovery machine causes knocking?

Back

Throttle the inlet as the machine manual directs if liquid causes knocking; liquid slugging can damage the compressor.

06
Front

What is vapor recovery used for after accessible liquid is removed?

Back

Vapor recovery removes refrigerant as a gas and is generally used to clear refrigerant remaining after accessible liquid has been recovered.

07
Front

In what order should refrigerant usually be recovered from a normally charged system?

Back

For a normally charged system, recover accessible liquid first when equipment and connections allow, then recover vapor.

08
Front

What evacuation levels apply to high-pressure appliances charged with 200 pounds or more?

Back

For appliances containing more than 5 pounds, high-pressure systems charged with 200 pounds or more require 4 in. Hg vacuum with pre-November 15, 1993 equipment, or 10 in. Hg with equipment made on or after that date.

09
Front

Why must a recovery cylinder be weighed during recovery?

Back

Weigh the cylinder throughout recovery and never exceed its marked fill limit. Liquid refrigerant expands as it warms.

10
Front

What is the main advantage of direct liquid recovery?

Back

Direct liquid recovery removes refrigerant through an appropriate liquid-side connection and can greatly shorten recovery time. Control flow, then continue with vapor recovery.

11
Front

What does liquid push-pull transfer, and what does it leave behind?

Back

Liquid push-pull uses pressure and a siphon effect to transfer accessible bulk liquid to the cylinder. It is not suitable for every system and does not remove remaining vapor.

12
Front

How should recovery be approached when a system has low charge or pressure?

Back

Recovery may be slow. Check for restrictions or leaks and use only manufacturer-approved methods to improve heat transfer or recovery rate; never use an open flame or vent refrigerant.