Timedora
Free Online Flashcard Deck

3 Type II: High- and Very-High-Pressure Appliances Free Online FlashCards

Study 3 Type II: High- and Very-High-Pressure Appliances with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

Which appliances are covered by EPA Section 608 Type II certification?

Back

Type II certification covers servicing or disposing of high- or very-high-pressure appliances, except small appliances and motor-vehicle air conditioners. It is required when work may release refrigerant.

02
Front

How does a psia pressure differ from a psig reading?

Back

A psia chart uses absolute pressure; a psig reading is lower by atmospheric pressure. At sea level, the difference is about 14.7 psi.

03
Front

What can indicate a refrigerant leak?

Back

Excessive superheat or oil traces around a leak on a hermetic system can indicate a leak.

04
Front

Which gases are appropriate for leak testing a refrigeration system?

Back

Use dry nitrogen alone, or nitrogen with a trace of refrigerant to help locate leaks. Never pressurize a refrigeration system with oxygen or compressed air; use a regulator and relief device with nitrogen.

05
Front

What are the traditional annual leak-repair trigger rates?

Back

For appliances containing 50 pounds or more of ozone-depleting refrigerant, the traditional annual trigger rates are 30% for industrial process refrigeration, 20% for commercial refrigeration, and 10% for comfort cooling and other appliances.

06
Front

What does refrigerant recovery do?

Back

Recovery removes refrigerant and stores it in an external container; it does not necessarily clean or test the refrigerant. Do not intentionally vent refrigerant during service.

07
Front

What recovery approach usually speeds refrigerant removal?

Back

Recovering liquid refrigerant first usually speeds recovery. Recovery may also be sped up by chilling the cylinder or carefully warming the appliance or vessel, within equipment limits.

08
Front

What can a pressure rise after evacuation indicate?

Back

After reaching the required evacuation level, wait a few minutes and check pressure. A rise can mean refrigerant remains in liquid form or is coming out of oil, so continue recovery as needed.

09
Front

What evacuation level applies to a very-high-pressure appliance?

Back

Very-high-pressure appliances require 0 inches Hg vacuum, whether recovery equipment was made before or after November 15, 1993.

10
Front

How should leaking components be handled when they prevent full evacuation?

Back

If a leak prevents the required level, isolate leaking components where possible. Evacuate sound components to the required level; recover from leaking components to the lowest attainable level without substantial contamination, but not above 0 psig.

11
Front

What is the maximum fill level for a recovery cylinder?

Back

Use only approved, reusable recovery cylinders; never refill disposable cylinders. Do not fill a recovery cylinder beyond 80% of its capacity because liquid expansion can create dangerous pressure.

12
Front

Can a hermetic compressor be energized while under vacuum?

Back

Do not energize a hermetic compressor while it is under vacuum. Follow electrical lockout and equipment procedures before service.