When recharging a centrifugal chiller, introduce vapor before liquid through the .
4 Type III: Low-Pressure Appliances Online Quiz Questions
Use this free practice quiz with 20 questions to review 4 Type III: Low-Pressure Appliances, test your knowledge, and prepare for your next test or exam.
When practical, which sequence should a technician use to recover refrigerant from a chiller?
- A
Recover vapor first, then liquid.
- B
Recover liquid first when practical, then recover the remaining vapor.
- C
Mix refrigerants to simplify recovery.
- D
Open the appliance before reaching its recovery endpoint.
What equipment can help identify a leaking chiller tube?
A low-pressure chiller requires leak testing. Which approach uses a preferred pressurization method?
- A
Pressurize with oxygen or compressed air.
- B
Use nitrogen as the preferred method in every case.
- C
Use controlled hot water or a built-in heating/pressurization device.
- D
Run the purge unit continuously instead of pressurizing the system.
For Type III exam review, what is the maximum nitrogen pressure for leak-testing a low-pressure centrifugal chiller? Enter the value in psig.
Select all correct steps or conditions for removing oil from a low-pressure appliance.
- A
Heat the oil to about 130°F before removal.
- B
Bring the appliance or isolated section to no more than 5 psig before removing oil.
- C
Raise the appliance pressure above 5 psig to release dissolved refrigerant.
- D
If draining into a receiver, bring the receiver to no more than 5 psig.
During chiller evacuation, circulate or remove water from the tubes as appropriate to .
What is the standard Section 608 evacuation target for a low-pressure appliance? Enter the pressure value in mm Hg absolute.
A leak prevents a low-pressure appliance from reaching its normal evacuation level. Select all correct actions described for this situation.
- A
Evacuate non-leaking components to the required level where possible.
- B
Leave non-leaking components unevacuated if any section is leaking.
- C
Evacuate leaking sections to the lowest attainable level, not above 0 psig.
- D
For leaking sections, always exceed 0 psig to reach the normal target.
Before applying a leak-rate threshold or reporting requirement to a chiller, what should a technician do?
- A
Apply the same leak-rate threshold to every chiller.
- B
Identify the relevant appliance, refrigerant, charge, and regulatory program before applying a threshold.
- C
Use purge frequency alone to determine the applicable leak-repair threshold.
- D
Apply a threshold based only on the chiller's size.
A low-pressure chiller needs frequent purging. What should this clue prompt a technician to investigate?
Explain how the standard low-pressure appliance evacuation target differs from the special procedure that may apply to certain non-major repairs not followed by evacuation to the atmosphere.
In a water chiller cycle, which process occurs in the condenser?
- A
It absorbs heat from building water and boils refrigerant into vapor.
- B
It rejects heat from refrigerant and condenses it into liquid.
- C
It compresses refrigerant vapor to raise its pressure and temperature.
- D
It lowers liquid refrigerant pressure before it returns to the evaporator.
A leak develops in an evaporator operating below atmospheric pressure. What can happen?
- A
Refrigerant always flows outward, while air and moisture are blocked.
- B
Air enters only if the purge unit is switched off.
- C
Air and moisture can be drawn into the system through the leak.
- D
The leak immediately raises the system above atmospheric pressure.
If a low-pressure chiller’s purge unit operates frequently, this alone identifies the location of the leak.
- A
True
- B
False
You need to raise pressure to leak-test a low-pressure centrifugal chiller. Which approach follows the recommended method and nitrogen limit?
- A
Use controlled hot water or a built-in heating/pressurization device when appropriate; if nitrogen is used, stay at or below 10 psig.
- B
Use compressed air and increase pressure until the leak becomes audible.
- C
Use oxygen at 10 psig because it is the preferred test gas.
- D
Use nitrogen at 10 psig as a required target, regardless of the appliance’s rated limits.
When recovering refrigerant from a chiller, which sequence is recommended when practical?
- A
Recover vapor first, then leave any liquid refrigerant in the appliance.
- B
Recover liquid first when practical, then recover the remaining vapor.
- C
Mix refrigerants to make recovery faster.
- D
Release liquid refrigerant before connecting recovery equipment.
During chiller evacuation, refrigerant pressure and temperature are falling. What should you do about water in the tubes?
- A
Close the water circuit and leave the tubes full throughout evacuation.
- B
Add compressed air to the water circuit to maintain tube temperature.
- C
Circulate or remove water from the tubes as appropriate to prevent freezing.
- D
Drain the refrigerant before evacuation so the water remains warm.
A technician is filling a refrigerant recovery cylinder. The cylinder is intended for refrigerant and has reached 80% of its capacity. Is it acceptable to stop filling at this point?
- A
True
- B
False
An equipment room may be oxygen-deficient. A technician who lacks the required training and equipment should not enter the room.
- A
True
- B
False
Related study packs and tools
- Quiz
1 High- and Very-High-Pressure Refrigeration Systems
A medium-difficulty quiz on EPA pressure categories, refrigeration-cycle components, pressure behavior, and safety hazards.
EPA 608 Type IIUpdated - Study guide
1 Refrigerant Types and Properties
Learn how refrigerant families differ in applications, environmental effects, operating conditions, safety classifications, equipment compatibility, and handling requirements.
EPA 608 RefrigerantsUpdated - Flashcards
3 Environmental Effects and Refrigerant Regulations
Learn how refrigerants affect ozone and climate, how regulations govern their use, and how to handle and select them responsibly.
EPA 608 RefrigerantsUpdated - Study guide
3 Environmental Effects and Refrigerant Regulations
Learn how refrigerants affect ozone and climate, how regulations govern their use and release, and what environmental and safety factors shape refrigerant selection.
EPA 608 RefrigerantsUpdated - Quiz
3 Safe Refrigerant Handling
A medium-difficulty quiz on applying safe refrigerant-handling practices, including hazard recognition, protective measures, leak response, and exposure response.
EPA 608 CoreUpdated - Flashcards
4 Safe Refrigerant Handling
Learn how to identify refrigerants, manage their hazards, recover and handle them safely, and prevent leaks.
EPA 608 RefrigerantsUpdated - Quiz
4 Safe Refrigerant Handling
A medium-difficulty quiz on identifying refrigerants, managing hazards, using equipment safely, preventing leaks, and handling cylinders.
EPA 608 RefrigerantsUpdated - Quiz
5 Chiller Service Practice and Verification
Practice chiller recovery, safety checks, endpoint verification, and service documentation. Follow equipment-specific procedures and applicable requirements.
EPA 608 Type IIIUpdated - Study guide
5 Chiller Service Practice and Verification
A practical framework for safely recovering refrigerant from chillers, verifying recovery and dehydration endpoints, troubleshooting problems, and documenting service work.
EPA 608 Type IIIUpdated - Quiz
5 Refrigerant Compliance Practice
Practice applying refrigerant compliance rules to equipment identification, refrigerant handling, technician qualifications, transfers, and recordkeeping.
EPA 608 CoreUpdated - Study guide
5 Refrigerant Compliance Practice
A practical guide to checking refrigerant rules, assigning work appropriately, preventing releases, handling recovered refrigerant, and keeping the records required for specific jobs.
EPA 608 CoreUpdated - Quiz
5 Small Appliance Service and Compliance Workflows
A medium-difficulty quiz on identifying small appliances and applying Section 608 service, recovery, leak-check, and disposal practices.
EPA 608 Type IUpdated