When is EPA Section 608 certification generally required?

Back

EPA Section 608 certification is generally required for work on stationary equipment that could reasonably be expected to release refrigerant.

02
Front

How can chlorine-containing refrigerants deplete stratospheric ozone?

Back

Ultraviolet radiation breaks down chlorine-containing chemicals in the stratosphere, releasing reactive chlorine that destroys ozone.

03
Front

Does Section 608 cover some refrigerants that do not deplete ozone?

Back

Section 608 also covers many refrigerant substitutes, including HFCs, even though HFCs do not deplete ozone.

04
Front

What injury can liquid refrigerant cause on contact with skin?

Back

Liquid refrigerant contacting skin or eyes can cause a cold burn.

05
Front

What is the maximum general fill level for a recovery cylinder?

Back

Do not fill a recovery cylinder beyond 80% of its rated capacity by weight; warming refrigerant expands and can raise pressure dangerously.

06
Front

Can disposable refrigerant cylinders be refilled?

Back

Disposable refrigerant cylinders must not be refilled.

07
Front

What gas should be used to pressure-test a refrigeration system?

Back

Use dry nitrogen with a regulator and suitable pressure-relief protection. Never use oxygen or compressed air.

08
Front

What should a technician do before recovering refrigerant?

Back

Identify the refrigerant first, then use recovery equipment and a cylinder suitable for it.

09
Front

What does recovering refrigerant mean?

Back

Recovering means removing refrigerant from an appliance and storing it in an external container; it need not be cleaned or tested.

10
Front

What does recycling refrigerant involve?

Back

Recycling cleans recovered refrigerant for reuse, generally in equipment belonging to the same owner, but does not ensure reclamation purity.

11
Front

What distinguishes refrigerant reclamation?

Back

Reclaiming reprocesses refrigerant to the applicable purity standard and verifies that it meets that standard.

12
Front

What does Section 608 generally prohibit during equipment service?

Back

Section 608 generally prohibits intentionally venting covered refrigerants while maintaining, servicing, repairing, or disposing of equipment.