What appliances does Type III certification focus on?

Back

Type III certification covers servicing, repairing, and disposing of low-pressure appliances, especially centrifugal chillers.

02
Front

Why can low-pressure chillers draw air and moisture through a leak?

Back

Because the system may be below atmospheric pressure, a leak can draw air and moisture inward.

03
Front

What can excessive purge-unit operation signal?

Back

Excessive purge-unit operation can signal that air is leaking into the low-pressure system.

04
Front

What is the preferred way to raise pressure for a low-pressure leak test?

Back

Controlled heating, such as hot water or a built-in heating device, is the preferred way to raise pressure for a low-pressure leak test. Nitrogen is another method where permitted.

05
Front

What is the maximum leak-test pressure for a low-pressure centrifugal chiller?

Back

A low-pressure centrifugal chiller must not be pressure-tested above 10 psig.

06
Front

What is a limitation of a pressure-decay test?

Back

A pressure-decay test can show that pressure is dropping, but it cannot pinpoint the leak's location.

07
Front

In what order should refrigerant be recovered?

Back

Recover liquid refrigerant first, then recover vapor; removing liquid first speeds recovery.

08
Front

What should be done with chiller water during evacuation?

Back

Circulate or remove chiller water as needed to prevent it from freezing during evacuation.

09
Front

How should oil be prepared before removal?

Back

Heat the oil to 130°F before removing it to reduce refrigerant release.

10
Front

What should you do if pressure rises after reaching the recovery vacuum?

Back

A pressure rise can mean refrigerant remains in the system or is boiling out of the oil; continue recovery as needed.

11
Front

What is the normal evacuation endpoint for a low-pressure appliance?

Back

For normal opening or disposal, evacuate a low-pressure appliance to 25 mm Hg absolute, regardless of the recovery equipment's manufacture date.

12
Front

What pressure condition applies before a qualifying non-major repair?

Back

For a non-major repair that will not be followed by evacuation to the atmosphere, pressurize the appliance to no higher than 0 psig before opening, using a method allowed for that refrigerant.