Which equipment categories does Universal certification cover?

Back

Universal certification covers Types I, II, and III: small appliances, high- and very-high-pressure appliances, and low-pressure appliances.

02
Front

What exams are required for Universal certification?

Back

Pass the Core and all three type-specific exams through an EPA-approved organization. Universal testing must be closed-book and proctored; an open-book Core test does not count.

03
Front

Which appliances fall under Type I certification?

Back

Type I covers factory-made, charged, hermetically sealed small appliances containing 5 pounds or less of refrigerant.

04
Front

Which equipment does Type II cover?

Back

Type II covers high- and very-high-pressure appliances, except small appliances and motor-vehicle air conditioners.

05
Front

Which equipment does Type III cover?

Back

Type III covers low-pressure appliances.

06
Front

When can attaching gauges require Section 608 certification?

Back

Section 608 certification is generally required for servicing stationary refrigeration or air-conditioning equipment in ways that could release refrigerant, including attaching gauges.

07
Front

What is the general Section 608 rule on intentional refrigerant venting?

Back

Intentional venting of ozone-depleting refrigerants and most substitutes during service is prohibited, apart from limited regulatory exceptions.

08
Front

What gas should be used to pressure-test a refrigeration system?

Back

Use dry nitrogen with a regulator and suitable pressure-relief protection. Oxygen or compressed air can create fire or explosion hazards when mixed with oil.

09
Front

What does refrigerant reclamation involve?

Back

Reclaiming processes recovered refrigerant and verifies that it meets the applicable purity standard.

10
Front

Why must a recovery cylinder not be overfilled?

Back

Leave vapor space because liquid refrigerant expands as it warms; overfilling can create dangerous pressure.

11
Front

What are the general recovery requirements for small appliances?

Back

Generally, recover 90% if post-November 15, 1993 equipment is used and the compressor works, or 80% if it does not work or the appliance predates that date. Evacuation to 4 inches of mercury vacuum is an alternative.

12
Front

What happens to refrigerant through the four main cycle components?

Back

The evaporator absorbs heat as refrigerant boils; the compressor raises vapor pressure and temperature; the condenser rejects heat as refrigerant condenses; the metering device lowers pressure before the evaporator.