Timedora
Free Online Flashcard Deck

3 Type II: High-Pressure Appliances Free Online FlashCards

Study 3 Type II: High-Pressure Appliances with 12 free online flashcards. Review key terms, definitions, and concepts with this interactive flashcard deck.

12 cards
01
Front

What appliances does Type II certification cover?

Back

Type II covers servicing or disposing of stationary high- and very-high-pressure appliances, excluding small appliances and motor-vehicle air conditioners.

02
Front

What does refrigerant recovery mean?

Back

Recovering removes refrigerant from an appliance and stores it in an external container; it does not necessarily clean or process the refrigerant.

03
Front

Why recover liquid refrigerant first when practical?

Back

Recover liquid refrigerant first when practical; removing liquid before vapor can speed up recovery.

04
Front

How should a recovery cylinder be filled safely?

Back

Use a scale and never exceed the recovery cylinder’s rated fill limit.

05
Front

What is the rule on venting refrigerant during service?

Back

Do not intentionally vent refrigerant during service. Only limited, de minimis releases during good-faith recovery efforts, such as some hose-connection losses, are allowed.

06
Front

When must recovered refrigerant be reclaimed?

Back

Recovered refrigerant may generally return to the same appliance or another appliance owned by the same person. If ownership changes, an EPA-certified reclaimer must reclaim it.

07
Front

What evacuation level applies to very-high-pressure or under-200-lb high-pressure appliances?

Back

The table requires 0 in. Hg vacuum for very-high-pressure appliances and for high-pressure appliances charged with under 200 lb, regardless of recovery-equipment age.

08
Front

When may a technician evacuate only the section being serviced?

Back

For an appliance with more than 5 lb of refrigerant, recover refrigerant, including liquid, before opening. You may isolate and evacuate only the section being serviced if its refrigerant can be isolated to a system receiver.

09
Front

How should a leaking appliance be evacuated if the table level cannot be reached?

Back

If a leak prevents reaching the table level, isolate leaking and non-leaking sections where possible. Evacuate non-leaking sections to the table level; evacuate leaking sections to the lowest attainable level without substantial contamination, but not above 0 psig.

10
Front

What pressure is required before a qualifying non-major repair?

Back

For a non-major repair with no evacuation to the atmosphere afterward, bring a high- or very-high-pressure appliance to 0 psig or lower before opening. This differs from the table’s vacuum levels.

11
Front

When is system-dependent recovery equipment restricted?

Back

System-dependent recovery equipment generally cannot be used on appliances with a full charge over 15 lb unless it is permanently attached as a pump-out unit.

12
Front

What ODS leak rates trigger corrective action?

Back

For covered ODS appliances charged with at least 50 lb, corrective action is triggered when the 12-month leak rate exceeds 30% for industrial process refrigeration, 20% for commercial refrigeration, or 10% for comfort cooling and other covered appliances.