What does refrigerant recovery mean?

Back

Recovering removes refrigerant from an appliance and stores it in an external container; it does not require testing or cleaning.

02
Front

What can a pressure or vacuum decay test establish?

Back

A pressure or vacuum decay test can show that a system is leaking, but it does not by itself locate the leak.

03
Front

What is the rule on intentional refrigerant venting?

Back

Intentional venting during maintenance, service, repair, or disposal is generally prohibited. Limited de minimis releases during good-faith recovery or service are allowed.

04
Front

What vacuum endpoint can satisfy the small-appliance recovery requirement?

Back

For small appliances containing five pounds or less of refrigerant, evacuation to 4 inches of mercury vacuum is also recognized as meeting the recovery requirement.

05
Front

What pressure limit applies before removing refrigerant-containing oil?

Back

Before removing oil, reduce the pressure in the appliance or isolated section to 5 psig or less. Alternatively, drain the oil into a system receiver reduced to that pressure.

06
Front

What evacuation level applies to a newer high-pressure appliance charged with at least 200 pounds?

Back

For a high-pressure appliance with a charge of 200 pounds or more manufactured on or after November 15, 1993, the required evacuation level is 10 inches of mercury vacuum.

07
Front

Do Section 608 leak-repair requirements cover appliances using only HFC substitutes?

Back

Section 608 leak-repair requirements do not apply to appliances containing only substitute refrigerants such as HFCs.

08
Front

Which appliances generally fall under the AIM Act HFC leak-repair program?

Back

As of 2026, the program generally covers appliances with a full charge of at least 15 pounds of an HFC or HFC substitute with a GWP greater than 53. Residential and light-commercial air-conditioning and heat-pump appliances are exempt.

09
Front

What records must be kept when disposing of appliances containing 5–50 pounds of refrigerant?

Back

For disposal of appliances containing 5–50 pounds of refrigerant, keep recovery location and date, refrigerant type, monthly recovered quantities, and quantities transferred for reclamation or destruction. Retain these records for three years.

10
Front

What does refrigerant recycling do?

Back

Recycling cleans recovered refrigerant, typically by oil separation and filtration. It may be reused in equipment owned by the same person, but it is not reclamation.

11
Front

What distinguishes refrigerant reclamation?

Back

Reclamation reprocesses refrigerant to applicable purity specifications and verifies its purity using the prescribed analytical method. It must be performed by an EPA-certified reclaimer.

12
Front

When is an initial verification test performed?

Back

An initial verification test checks the repair before refrigerant is added back to the appliance.