Which appliances does Type II certification cover?

Back

Type II certification covers technicians servicing, repairing, maintaining, or disposing of medium-, high-, and very-high-pressure appliances, with specified exceptions for small appliances and vehicle air conditioners.

02
Front

What defines a high-pressure appliance?

Back

A high-pressure appliance uses a refrigerant with liquid-phase saturation pressure from 170170 to 355 psia355\ \text{psia} at 104∘F104^\circ\text{F}.

03
Front

What makes an appliance very-high-pressure?

Back

A very-high-pressure appliance uses a refrigerant with a critical temperature below 104∘F104^\circ\text{F} or saturation pressure above 355 psia355\ \text{psia} at that temperature.

04
Front

What does refrigerant recovery mean?

Back

Recovering means removing refrigerant from an appliance and storing it. Recovery alone does not clean or reclaim the refrigerant.

05
Front

When may system-dependent recovery equipment be used on a charge over 15 lb15\ \text{lb}?

Back

System-dependent recovery equipment cannot be used on an appliance with a full charge over 15 lb15\ \text{lb}, unless the equipment is permanently attached as a pump-out unit.

06
Front

What evacuation level applies below 200 lb200\ \text{lb} for a high-pressure appliance?

Back

For a high-pressure appliance charged with less than 200 lb200\ \text{lb}, the required evacuation level is 0 in. Hg0\ \text{in. Hg} vacuum, regardless of the equipment’s manufacture date.

07
Front

What vacuum level applies to a charge of at least 200 lb200\ \text{lb} with newer equipment?

Back

Use a vacuum level of 10 in. Hg10\ \text{in. Hg} for a high-pressure appliance charged with at least 200 lb200\ \text{lb} when the recovery equipment was made or imported on or after November 15, 1993.

08
Front

What vacuum level applies to a charge of at least 200 lb200\ \text{lb} with older equipment?

Back

Use a vacuum level of 4 in. Hg4\ \text{in. Hg} for a high-pressure appliance charged with at least 200 lb200\ \text{lb} when the recovery equipment was made or imported before November 15, 1993.

09
Front

What pressure is required before a qualifying non-major repair?

Back

For a non-major repair not followed by evacuation of refrigerant to the environment, bring a high- or very-high-pressure appliance to 0 psig0\ \text{psig} before opening it.

10
Front

What gas should be used for pressure testing?

Back

Use regulated nitrogen, with a pressure regulator and relief protection. Do not use oxygen or compressed air for pressure testing.

11
Front

Which appliances are covered by the EPA leak-repair program?

Back

It applies to appliances with a full charge of at least 50 lb50\ \text{lb} of ozone-depleting refrigerant. It does not apply to appliances containing only substitute refrigerants.

12
Front

What are the annualized leak-rate trigger percentages?

Back

The annualized leak-rate trigger is 30%30\% for industrial process refrigeration, 20%20\% for commercial refrigeration, and 10%10\% for comfort cooling and all other appliances.