What pressure criterion defines a low-pressure appliance?

Back

A Type III low-pressure appliance uses a refrigerant whose liquid-phase saturation pressure is below 45 psia at 104°F.

02
Front

Name two refrigerants commonly used in low-pressure appliances.

Back

Common examples include R-11, R-123, R-113, and R-245fa.

03
Front

What is the required evacuation endpoint for a low-pressure appliance?

Back

The required evacuation endpoint is 25 mm Hg absolute, regardless of charge size or recovery equipment manufacture date.

04
Front

In what order should refrigerant phases be recovered?

Back

Recover accessible liquid first to speed removal, then recover the remaining vapor.

05
Front

Why manage water in a chiller during evacuation?

Back

Circulate or remove the water as appropriate to reduce the risk of freezing and damaging chiller tubes.

06
Front

What should a technician do after reaching the evacuation endpoint?

Back

Wait a few minutes and check for pressure rebound. A rise can indicate refrigerant remains or is emerging from oil, so continue recovery as needed.

07
Front

What is the traditional recovery-unit high-pressure cutout value?

Back

The traditional Type III exam value for the recovery unit’s high-pressure cutout is 10 psig. This is an equipment setting, not the evacuation endpoint.

08
Front

What qualifies as a major repair on a low-pressure appliance?

Back

A major repair involves removing a compressor, condenser, evaporator, or auxiliary heat-exchange coil, or leaving an opening over 4 square inches uncovered for more than 15 minutes.

09
Front

What pressure applies to the non-major repair exception?

Back

For a qualifying non-major repair that will not be followed by evacuation to the atmosphere, pressurize the appliance to no higher than 0 psig before opening it; use heat to raise the pressure.

10
Front

What does a purge unit do in a low-pressure system?

Back

A purge unit removes air and other noncondensable gases, separates refrigerant from the purge stream, and returns that refrigerant to the system.

11
Front

What can unusually frequent purge operation indicate?

Back

Frequent or increasing purge operation is a warning sign of possible leakage. Investigate and locate leaks; purging is not a substitute for repair.

12
Front

What is the commonly taught maximum leak-test pressure for a low-pressure centrifugal chiller?

Back

For Type III exam preparation, 10 psig is the commonly taught maximum leak-test pressure for a low-pressure centrifugal chiller. Treat it as a ceiling, not a target.